"DALI Gateway C00CX2 EN / C00CX4 EN" software
Parameters
Best. Nr. 1060 00
Page 134 of 136
Reduced brightness
during pre-warning time
0.1 % … 100 %;
10 %
This parameter determines the reduced
brightness to be adjusted at the time of the
pre-warning.
The adjustable value is restricted by the
parameterized minimum and maximum
brightness. The standard setting will also
adjust accordingly.
The reduced brightness will not start the
shutoff function when it reaches or falls
short of the specified shutoff brightness.
This parameter will be visible only if the
Staircase timer function has been
activated.
Pre-warning time
00:01 … 59:59 [mm:ss]
30 s
This parameter is used for programming
the duration of the pre-warning time. The
pre-warning time is added to the switch-on
time. During the time parameterized at this
point, the reduced brightness will be
adjusted.
This parameter will be visible only if the
Staircase timer function has been
enabled and the pre-warning time has
been activated.