"DALI Gateway C00CX2 EN / C00CX4 EN" software
Parameters
Best. Nr. 1060 00
Page 131 of 136
Switch-on/switch-off behaviour
Selection of time delay
None
ON-delay
OFF-delay
ON-delay and OFF-delay
The “Switching” and “Switching central
function” communication objects can be
separately evaluated. This parameter is
used to define the desired mode of
operation of the time delay and to enable
the other delay parameters.
ON-delay time
00:00:01 … 23:59:59
[hh:mm:ss]
30 s
This parameter is used for programming
the duration of the ON-delay
This parameter becomes visible only if
the On-delay or the On and OFF-delay
has been activated.
ON-delay retriggerable ?
Yes
No
An active ON-delay can be retriggered by
another "1" telegram (setting "yes")
Alternatively, retriggering can be
suppressed (setting "No").
This parameter becomes visible only if
the On-delay or the On and OFF-delay
has been activated.
OFF-delay time
00:00:01 … 23:59:59
[hh:mm:ss]
30 s
This parameter is used for programming
the duration of the OFF-delay
This parameter becomes visible only if
the Off-delay or the On and OFF-delay
has been activated.
OFF-delay retriggerable
?
Yes
No
An active OFF-delay can be retriggered by
another "0" telegram (setting "yes")
Alternatively, retriggering can be
suppressed (setting "No").
This parameter becomes visible only if
the Off-delay or the On and OFF-delay
has been activated.
Soft-ON function ?
Yes
No
The Soft-ON function permits a slowed-
down switch-on of the DALI group. If the
function is activated (setting “Yes”) a
dimming operation is started until the
switch-on brightness is reached on
reception of a switch-on telegram via the
“Switching” or “Switching central function”
objects.