"DALI Gateway C00CX2 EN / C00CX4 EN" software
Parameters
Best. Nr. 1060 00
Page 111 of 136
Enable DALI device
replacement manually ?
Yes
No
After the start of the automatic device
replacement, the DALI Gateway can check
the DALI system via manual control for the
integrity of the DALI devices incorporated
in the system. Thus, the DALI Gateway is
able to detect, for example, replaced
electronic ballast devices and to program
them with the appropriate project data.
The automatic device replacement can be
initiated locally via manual control (press
the and ALL OFF key simultaneously at
least for 10 s) only if this parameter has
been set to „Yes“. If set to “No” a manual
operation will show no response.
Blinking rate
1 s
2 s
5 s
10 s
At the beginning and at the end of a disable
function, if used, groups can also be
parameterized to "blinking". In this case the
corresponding devices of the groups will
periodically change their switching status.
The "Blinking rate" parameter generally
defines the ON-time and the OFF-time of a
"blinking" signal for all groups.
Example:
Blinking rate = 1 s
1 s on
Æ
1 s off
Æ
1 s on
Æ
1 s off ...
Central function ?
Yes
No
The "Yes" setting enables the central
function and thus the "Central function"
object. An assignment of individual DALI
groups to the central function is possible
only if the function is enabled.
Central object polarity
0 = deactivated / 1 =
activated
1 = deactivated / 0 = activated
This parameter determines the polarity of
the central object.
This parameter becomes visible only if
the central function is enabled.