Order No. 2104 ..
4.2.4.4 Room temperature controller
The device can be used for single-room temperature control. Depending on the operating mode,
the current temperature setpoint and on the room temperature, command values for heating or
cooling control can be sent to the KNX. Usually, these command values are then converted by a
suitable KNX actuator, e.g. heating or switching actuators or directly by bus-compatible
actuating drives, evaluated and converted to physical variables for air conditioning control.
The room temperature control is an independent function section of the device. It has its own
parameter and object range in the ETS configuration. The room temperature controller is
therefore available independent of the function of the inputs, logic gates and humidity and CO
2
sensor.
4.2.4.4.1 Operating modes and operating mode change-over
Introduction
The room temperature controller distinguishes between two different operating modes. The
operating modes specify whether you want the controller to use its variable to trigger heating
systems ("heating" single operating mode) or cooling systems ("cooling" single operating mode).
You can also activate mixed operation, with the controller being capable of changing over
between "Heating" and "Cooling" either automatically or, alternatively, controlled by a
communication object.
In addition, you can establish two-level control operation to control an additional heating or
cooling unit. For two-level feedback control, separate command values will be calculated as a
function of the temperature deviation between the setpoint and the actual value and transmitted
to the bus for the basic and additional levels. The parameter "Operating mode" in the "Room
temperature control -> Controller general" parameter branch specifies the operating mode and,
if necessary, enables the additional level(s).
"Heating" or "cooling" single operating modes
In the single "Heating" or "Cooling" operating modes without any additional level, the controller
will always work with one command value and, alternatively, when the additional level is
enabled, it will use two command value in the configured operating mode. Depending on the
room temperature determined and on the specified setpoint temperatures of the operating
modes, the room temperature controller will automatically decide whether heating or cooling
energy is required and calculates the command value for the heating or cooling system. The
controller indicates whether it is currently heating or cooling by means of the objects "Heating
message" or "Cooling message". If it is defined in the configuration that a basic and additional
level are used, then the basis for the messages "Heating" and "Cooling" is the state that the
basic level is currently in.
Page 64 of 171
Software "KNX CO2 sensor"
Functional description