4.2.5.3 Push button interface parameter
Description
Values
Comment
h
Push button interface
Transmit delay after
reset or bus voltage
return
Base
130 ms
260 ms
520 ms
1 sec
2.1 sec
4.2 sec
8.4 sec
17 sec
34 sec
1.1 min
2.2 min
4.5 min
9 min
18 min
35 min
1.2 h
After reset or bus voltage return, the
application program of the push-button
interface can be disabled for a defined
time period until the corresponding
reactions are executed.
No pending signals will be evaluated on
the inputs during this time! Even a
feedback will only be transmitted after
the time delay has elapsed at the
earliest.
Determines the time base of the time
delay.
Time = Basic x Factor
Transmit delay after
reset or bus voltage
return
Factor (3...127)
3...
17
...127
Determines the time factor of the time
delay.
Time = Basic x Factor
Presetting: 1 s × 17 = 17 s
Debouncing of the
button inputs
Base
0.5 ms
Specifies the time for software
debounce for all the binary inputs. On
the basis of the time set here, a signal
edge is evaluated at the input with a
delay.
Time = Basic x Factor
Debouncing of the
button inputs
Factor (10...255)
0...
60
...255
Specifies the time for software
debounce for all the binary inputs. On
the basis of the time set here, a signal
edge is evaluated at the input with a
delay.
Time = Basic x Factor
Presetting: 0,5 ms × 60 = 30 ms
Telegram rate
limit
enabled
disabled
The telegram rate limit can be disabled
or enabled. If telegram rate limitation is
enabled, no telegram will ever be
transmitted within the first 17 seconds
after bus voltage return!
Telegrams per 17 s
30
60
If telegram rate limitation is enabled, the
maximum number of telegrams in 17
Page 142 of 171
Software "KNX CO2 sensor"
Parameters