Transmission interval

1 … 60 min
Basic setting: 15 min

The current consumption data
is transmitted at the interval
set here at the latest. Changes
to the effective output cause
fresh transmission, however
only after one minute at the
earliest. 

Rel. threshold value, effective
output 

1 ... 50 %
Basic setting: 10 %

The transmission of
consumption data can be
coupled to the change in
effective output. The basis is
always the most recently
transmitted effective output
value. If the percentage
change entered here is
exceeded, then all the
measured values are resent.

Abs. threshold value, effective
output 

0 … 2000 W
Basic setting: 1 W

A lower threshold value of the
effective output can be
entered here, to avoid
frequent transmission in the
lower power range. Event-
controlled transmission is only
active above this threshold
value.

Suppression length, effective
output 

0 ms … 300 s
Basic setting: 0 ms

Triggers for event-controlled
transmission are often switch-
on and switch-off operations.
In order to avoid incorrect
measured values due to
switch-on peaks, this
parameter can be used to
enter a suppression period.
The measured values are only
transmitted if the effective
output is still above or below
the relative threshold value
after the set time. 

Averaging length

0.2 … 300 s
Basic setting: 1 s

In the case of effective output,
it is not the current value
which is transmitted, as with
other measured values, but
the average value. It is
possible to set the period for
average value formation here.

Information window

During channel selection in the Information window, the following values are displayed.

Display value

Explanations

Measuring status:
value is real/
out of service

value is real: Device being operated
out of service: Device error

Measuring status:
no fault/
value is corrupted due to failure

no fault: Measurement active
value is corrupted due to failure: The sensor is
not supplying valid measured values.

Measuring status:
in commission

Not used.

32582202

10499462

13.03.2014

5/7

eNet

Radio energy sensor, 1-gang intermediate plug

Содержание 5472 02

Страница 1: ...part of the eNet system High transmission reliability at a radio frequency of 868 MHz is achieved by the transmission behaviour and bidirectional data transfer The range of a radio system depends on...

Страница 2: ...alue effective output 1 W Transferred characteristic electric values Current Voltage Average effective output Interval for average formation configurable between 0 2 300 s Apparent output Fundamental...

Страница 3: ...e is reset to default setting 5 Appendix The icon confirms the conformity of the product to the relevant guidelines 5 1 Technical data Rated voltage AC 230 V Mains frequency 50 60 Hz Rated load curren...

Страница 4: ...e current voltage value Transmit current On Off Basic setting On Transmits the current current value Transmit effective output On Off Basic setting On Transmits the average effective output If negativ...

Страница 5: ...transmission are often switch on and switch off operations In order to avoid incorrect measured values due to switch on peaks this parameter can be used to enter a suppression period The measured val...

Страница 6: ...ed effective energy Counter status can be set via settings window i The value can be updated using the arrow next to the display values 5 3 Troubleshooting Negative effective output or energy values a...

Страница 7: ...Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32582202 10499462 13 03 20...

Отзывы: