General safety instructions 

Electrical devices may only be installed and 
mounted by qualified electricians.

Serious injury (e.g. caused by an electric 
shock), fire, or material damage is possible 
if mounted improperly. 
Read these instructions thoroughly and 
observe them.

These instructions are part of the product 
and must remain with the end customer.

Product features

Thanks to its innovative single-screw 
installation system (ESM system), the key 
switch insert 10 A/240 V offers important 
advantages:

• Fast installation and removal of the entire 

switch

• Screwless installation of the locking panel 

(plug-in installation)

• Screwless installation of the electrical 

contact (plug-in installation)

• Ideal security due to interior lid and flush 

half-cylinder profile

• Universal use as surface-mounted or 

flush-mounted key switch insert

Scope of supply

• 1x key switch insert
• 1x installation and operating instructions

Ensure the package contents are 
complete and undamaged. 
When filing complaints, see "Warranty".

Necessary accessories

• Half-cylinder profile, sorted locking type 

(Order No. 0001 00)

• Half-cylinder profile, same locking type 

(Order No. 0002 00)

• Half-cylinder profile, VdS Class B 

(Order No. 0003 00)

Accessories

• Cover plate with symbol (Order No. 0097 30)

• Cover plate without symbol 

(Order No. 0098 30)

• Blind controller insert with auxiliary input 

(Order No. 0389 00)

Preparation

Prior to installation, first disassemble the 
key switch insert as described below.

1. Loosen screw (1) and remove front 

panel (2).

2. Carefully pull out seal (3) and lid (4).

3. Push locking panel (5) up (= unlocked) 

and pull it out.

4. Remove switching insert (6) from the 

housing (7).

5. Connect protective conductor on the 

housing (see arrow).

Switching insert – front and rear

6. Wire the switching insert depending on the 

use.

2

3

4

5

6

7

1

2I

1I

PI

1

2

P

Switch, 1-pole 2-pole (Order No. 0144 30)

Push button, (Order No. 0163 30)

Installation

1. Switch the mains voltage off.

2. Install housing.

3. Return the switching insert in the housing 

and tuck the cable in carefully.

4. Insert locking panel and push it down 

(= locked).

5. Install half-cylinder profile: insert from 

behind through the opening in the lid and 
fasten it using the enclosed locking pin 
(from left to right for flush-mounted 
installation; from right to left for surface-
mounted installation). Insert key into the 
half-cylinder profile and turn it (45° position 
to the right) so that the cylinder flange is 
congruent with the locking panel.

6. Insert lid into the housing.

7. Insert seal.

8. Put on front panel and refasten it with the 

screw.

9. Switch on mains voltage.

Technical data

i

Installation

Observe the following when installing the 
housing:

• "Surface-mounted" (= APZ) or "flush-

mounted" (= EPZ) installation is possible.

• The opening for the water outlet must 

always be on the bottom.

• First, break out one of the three cable 

openings (on the top, bottom, or rear of 
the housing).

• Use a screw joint (M20) with lock nut to 

fasten the housing.

Operating voltage:

AC 240 V

Utilisation category:

AC15

Conventional 
thermal current:

16 A

Operating current:

5 A

Isolation voltage:

300 V

Contacts:

2

Connections:

max. 2.5 mm

2

Type:

Screw terminal

Housing
Material:

Diecast aluminium

Dimensions (WxHxD):

75 x 75 x 66 mm

2

1

P

M

L

2I

1I

PI

N

2

1

P

M

L

N

X0

21

3  12/

1

6

Key switch 
10 A 240 V~ for all 
DIN half-cylinder 
profiles

Switch, 2-pole

0144 30

Push button, 1-pole

0163 30

Operating instructions

EN