Ginlong Solls-50K-US Скачать руководство пользователя страница 1

Содержание Solls-50K-US

Страница 1: ...8408 I Email les ginlong m I sales ginlong usa m Web www ginlong m I www ginlong usa m Please record the 8erial number ofyourinverter and quote this when you contact U8 us Intertek solis PV Utility I...

Страница 2: ...equipment has sup ied The customer is fully liable for any modifications made to the system therefore any hardware or software modification manipulation or alteration not expressly agreed with the man...

Страница 3: ...o terminals M 20 3 5 4 1 Using spring terminal 20 3 6 Making connections to the AC side ofthe inverter 21 3 6 1 Connecting the inverter to the utility grid 21 3 6 2 Wiring procedure 22 3 7 External gr...

Страница 4: ...meter 43 6 7 13 Fan Test 43 7 Maintenance 44 7 1 For inverter model with Fan 44 8 Troubleshooting 47 8 1 Current alarm 47 8 1 1 Running messages 47 8 2Alarm history 47 8 2 1 Viewing alarm history 47 8...

Страница 5: ...st be betw n 16 and 140 F 26 60C and humidity should be belween 0 to 100 non ndensing Do not stack mo than lwo 2 inver rs high Keep the box es away from rrosive m rials avoid damage to the inverter en...

Страница 6: ...sed and this can only be done by a service technician The warranty may be voided if any unauthorized removal of coveroccurs CAUTION The inverter s surface temperature can reach up to 750C 1670F To avo...

Страница 7: ...ng with firmware has been designed to determine ifthe grid is present by adjusting the output frequency of the inverter In the case of a 60Hz resonant system where the inverter is pa ially isolated fr...

Страница 8: ...face 3 1 2 4Air circulation J J 00 not install in small closed rooms where air cannot freely circulate To prevent overheating always ensure that the air w around the inve er is not blocked 12 3 Instal...

Страница 9: ...fans may be mounted at 15 90 degrees off horizontal 1 Referring to Figure 3 4 select the mounting height of the brackel For brick walls lhe position ofthe holes should be suitable for expansion bolts...

Страница 10: ...t with screws 3 Installation 3 4 Wiring box configuration The Solis U S Three Phase Inverter wiring box is designed for easy access to all connection terminals including monitoring communication ports...

Страница 11: ...18 hlgh vollag pre nl wfl8n PV modul 818 B d10IIghtcau lng a rt8kofd8alh dU810 an 18Clrtc ck m touchlng a DC conductorl OnJyconn ctth8 DC cabl from th8 PV modul81othe i 8rt8rasd crib d in thi manual...

Страница 12: ...nals marked L L2 and L3 Referto local code and voltage drop tables to determine the appropriate wire size and type 2 Connect the grounding conductor to the terminal marked PE protective earth the grou...

Страница 13: ...tor cables strip the end ofAC cable outer insulating jacket about 3 inches Strip the end of each wire as shown in figure 3 12 1 L2 L3 Figure 3 13 3 7 External ground connection point An OPTIONAl exter...

Страница 14: ...connactlon of RJ45 network po When using terminal5 RJ45 connector to connect use the following wiring sequence Connect the Ethernet cable according to the TIAlEIA 568B standard Insertthe wire into th...

Страница 15: ...to highlighlADVANCED SETTINGS Press enterto select Im h 61mtj1 Settings Figure 5 1 2 The screen will showthat a password is required The default password is 0010 press the DOWN key to move cursor pre...

Страница 16: ...ositive and negative wires ofeach string Ifthe open circuitvoltage ofthe string is near the maximum value accepted by the inve er verifythe string length Low ambient temperatures cause an increase in...

Страница 17: ...inverter will turn on The red DC POWER LED and LCD will be continuously lit Solis inverters are powered from the DC side When the inverterdetects DC power that is within start up and operating ranges...

Страница 18: ...al operation Display Duration Description V DC1 350 8V 10sec V_DC1 Shows input 01 voltage value I DC1 5 1A I_DC1 Shows input 01 current value V l DDCC4425EDTEASV l l 10sec V_DC4 Shows input 02 voltage...

Страница 19: ...vious menu 34 6 Normal operation 6 6 Advanced Info Technicians Only Access to this area is forfully qualified and accredited technicians only A NmE A password is required to access Advanced Info and A...

Страница 20: ...5 Monthly Energy and Yearly Energy These two options are for viewing the energy generation for selecled month or year YES ENT NO ESC I I YES ENT NO ESC Selecl 2015 I I Selecl 20 F ure6 10Se t month fo...

Страница 21: ...nuallythus creating a custom grid profile by using this function 38 6 Normal operation Solis 50K US ISolis OK US FISolis 60K US FI Solis 66K US F V G V1 236 335V V G F1 60 2 63Hz V G V1 T 0 1 95 V G F...

Страница 22: ...ll pr event the inverterf rom r eaching maximum power 6 7 6 Calibrate Energy Maintenance or replacement could clear or cause a differentvalue to display for total energy Use this function to allow the...

Страница 23: ...ction reboots the HMI and LCD display 42 6 Normal operation 6 7 12 Debug Parameter A isap Debug Parameter as shown as below U16DAT1 0000 U16DAT2 0000 U16DAT3 0000 U16DAT4 0000 U16DAT5 0000 U16DAT6 000...

Страница 24: ...too dirty to read A NOTES Never use any solvents abrasives or corrosive materials to clean the inverter 7 1 Inverter models with fan assisted cooling The function ofthe fan is to assist the convectio...

Страница 25: ...rvice at hUD llwww ainlona com en Loain htmlar 1 866 438 8408 Dlease have available the followino Please have the following information available when contacting technical support 1 Inve er serial num...

Страница 26: ...l DC Switch ON T st DC 8wilch OFF CheckAC at the inverter Check grid standard Replace inverler IfAC measures high adjusl upper limit wilh Tesl DC witch OFF permlsslon 1rom utlllty Check OC at the inv...

Страница 27: ...erature Is inverler in direct sunshine Protection ambient lamperature 60C Measure ambienl temperature near inverler Iftemp is in range replace inverler Protection DC class 11 andACclass 111 optional I...

Страница 28: ...on DC class 11 and AC class III optional Protection DC class 11 andACclass 111 optional Slze lnch 24 8W 40 7H 13 9D Slz Inch 24 8W 40 7 13 9D Weighl 1721b Weight 1721b T pology Transformerlass T pol g...

Страница 29: ...1O Appendices 10 1 AppendixA Part Torque ACTerminal 3 6 Nm DC Fuse Teminal 1 5 1 7 Nm Screw ForWiring Box Cover 1 8 2 0 Nm Ground Terminal 3Nm Figure 10 1 54...