Caution
: Installing the switch in a rack requires two people. One person should
position the switch in the rack, while the other person secures it using the rack screws.
Adjust Rear-Post Bracket Ears
1. Lock the position of the rear-post bracket ears using the included position-locking
screws. You can also adjust the rear-post bracket ears to fit different rack depths
from 56 cm to 75 cm.
Basic Connections and Configuration
This chapter describes how to establish your first configuration session with the GigaVUE
TA Series Traffic Aggregator and set the basic initial configuration options necessary to
get you up and running.
Refer to the following sections for details:
Grounding the GigaVUE-TA25E
To ground the GigaVUE-TA25E do the following:
1. .Ensure the rack is properly grounded and in compliance with ETSI ETS 300 253.
Verify that there is a good electrical connection to the grounding point on the rack
(no paint or isolating surface treatment).
2. Attach the grounding wire (#14 AWG) to the grounding point on the switch rear
panel. Then connect the other end of the wire to rack ground.