9. Service position
- Release the quick release fasteners
- Remove the base plate from the housing
- Attach the base plate with the clips to the two upper
screws (Service position).
During assembly, insert the base plate into the housing and
secure with the quick release fasteners.
Caution! Ensure the base plate
is correctly seated in the housing.
10.Replacing the nozzle
- Attach the base plate in the Service position.
- Release ignition cable from the ignition electrode.
- Release accumulator plate and withdraw upwards.
- Release oil nozzle (spanner SW16), in doing so ensure the
nozzle holder is secured against turning via spanner SW 16.
- Replace oil nozzle.
11.Setting the ignition electrodes
The electrodes are factory-set. The specified measurements
serve for checking purposes.
12. Setting the air volume measure "A"
Measure "A"
Measure "A"
(see adjustment table, page 15)
serves as
an orientation guide for setting the burner. Measure "A" de-
scribes the position of the nozzle holder with accumulator
plate in the burner pipe taper.
Example: Turn adjusting nut clockwise
Air throughput increases, the CO
2
content in the exhaust gas
decreases. The correct setting of measure "A" is checked by
measuring the CO
2
at the measuring point in the exhaust gas
pipe.
Stop for
accumulator plate
3 with 60° nozzles
5 with 45° nozzles