Giacomini K492DY012 Скачать руководство пользователя страница 1

1

0954EN  June 2018

R

oom

 

contRol

 

and

 

electRonic

 

Regulation

W

eekly

 

chRonotheRmohumidistat

foR

 

exteRnal

 

Wall

-

mount

 

installation

k492dy012

Description

Room chronothermohumidistat 

K492DY012 

for external wall-mount 

installation including temperature and relative humidity sensor with two side 
relays, controls heating/cooling systems and one dehumidifier at the same 
time. The unit can be programmed weekly, with daily timer and manually.

Versions and product codes

Product code

Power supply

K492DY012

230 V

Accessories

• K463PY001:

 immersion delivery temperature probe

Description of display keys

1

5

8

2

3

7

6

4

Legend

1

Day of the week

2

Activation status: cooling or heating

3

Room temperature (Celsius / Fahrenheit)

4

Multifunction key icons

5

Multifunction keys

6

Activation status: dehumidification

7

Operation mode

8

Bar graph to display messages and daily program

Notes

 The display lights up by pressing any key once.

 The function of each key varies with each program and it is shown on 

the display near the corresponding button.

Technical data

 

Temperature range

2÷40 °C, increase 0,1 °C

Room T measuring range / display

-50÷50 °C

Relative humidity regulation range

30÷70 %, increase 1 %

Room relative humidity measuring 

range /display

0÷100 %

Power supply

230 V, 50 Hz

Max. absorbed power

5 W

Type of output

2 relays with dry changeover contact 

(COM/NA/NC)

3 screw clamps ( open)

Type of input

 1 auxiliary probe - NTC 10K - Lmax 100 m 

  section 0,5÷1,5 mm

2

 (K463PY001)

 2 auxiliary inputs - free contacts

Back-up battery

For program and clock/calendar

Contact capacity

5(3)A 250 Vca

Type of action

1 B.U. (connection micro-switch)

Software

class A

Min. regulation differential

0,1÷5 K

Thermal gradient of reference

4 K/h

Max. room temperature

45 °C

Storage temperature

-10÷60 °C

Electric insulation

Double insulation

Protection class

IP30

Pollution degree

2

Pulse voltage

4000 V

Installation

Wall/flush mounting box

Dimensions

137 x 90 x 32 mm

Standards

EN 60730-1 standard and second parts

ErP class

ErP Class V; 3%

[Reg. EU 811/2013 - 813/2013]

K492DY012