TTM-000W Series
26 / 37
BA_MA_TTM-00XW_EN_V1.00
6.5
Event Output 1/2
No. Character
Name
Description
Initial Value
1
5Et
3
4
Setting Mode Selection
Screen
EV Output 1 Setting Mode
EV Output 2 Setting Mode
Settings of the Event Output 1 Function.
Settings of the Event Output 2 Function.
2
_
E F
Setting of Event Output □
Function
(PV Event)
00
_
E F
①②
PV Event Function
②
Type
0
OFF
1
Upper & Lower Limit Deviation, 1
– 0 – 1
2
Upper Limit Deviation, 0
– 1
3
Lower Limit Deviation, 1
– 0
4
Deviation Range, 0
– 1 – 0
5
Upper & Lower Limits, 1
– 0 – 1, absolute
6
Upper Limit, 0
– 1, absolute
7
Lower Limit, 1
– 0, absolute
8
Range, 0
– 1 – 0, absolute
Additional Function
①
Type
0
OFF
1
Keep
2
Standby Sequence
3
Keep + Standby Sequence
3
4
_
E x
_
E L
Event Output □ Upper Limit
Setting
Event Output □ Lower Limit
Setting
Thermocouple/Resistance Temperature Detector Input Model
Setting Range: -1999-3276 or -199.9-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: -1999-9999
(Decimal point is at the designated position)
Setting Unit: digit
5
_
E
C
Setting of Event Output □
Sensitivity
Input Type of Thermocouple/Resistance Temperature Detector
Setting Range: 0-999 or 0.0-999.9
Setting Unit:
℃
0
Current and Voltage Input Model
Setting Range: 0-9999 (Decimal point is at the designated position)
Setting Unit: digit
6
_
E t
Event Output □
Delay Timer Setting
Setting Range: 0-9999 seconds
0