6 | Operation
OMNIPLUS-F
32/ 45
C-E01_X__OMNIPLUS-F__DB2-1.0
6.8.2.4 "Switch logic" parameter
Switching logic
Setting values:
Alarm low: When an alarm event occurs, the output status changes from
High to Low signal
Alarm high: When an alarm event occurs, the output status changes from
Low to High signal
6.8.2.5 "Setpoint 1" / "Setpoint 2" parameter
Limit value for flow or temperature, display depends on selection under "Function" and
"Switch mode".
Setting values:
The setting range corresponds to the measuring range of the measurand selected for
the output (flow or temperature). The display shows the selected unit and number of
decimal places.
Setpoint 1" is used in the two single point modes.
In Window mode "Setpoint 1" and "Setpoint 2" are used.
In the "Single point max" mode, an alarm is triggered when "Setpoint 1" is exceeded.
The alarm is reset when "Setpoint 1" - "Hysteresis" is not reached.
In the "Single point min" mode, an alarm is triggered when "Setpoint 1" is not reached.
The alarm is reset when "Setpoint 1" + "Hysteresis" is exceeded.
In Window mode, an alarm message is issued when "Setpoint 1" is exceeded, or
Falling below "Setpoint 2". If the value of "Setpoint 1" is smaller than that of
"Setpoint 2" an alarm message occurs in the window between the two values.
Outside the window, the alarm is reset.
6.8.2.6 "Hysteresis" parameter
Hysteresis for the limit value(s).
The hysteresis is the amount of measured value change required to reset a limit
alarm. The setting is made with the unit and number of decimal places selected for the
measured variable.
Settings example 1:
Switching Mode: Single point min mode
Setpoint 1:
5.0 l/min
Hysteresis:
0.5 l/min
An alarm is triggered when the flow rate falls below 5.0 l/min. If 5.5 l/min is exceeded
(5 + 0.5 l/min), the alarm is reset.
Settings example 2:
Switching Mode: Single point max mode
Setpoint 1:
5.0 l/min
Hysteresis:
0.5 l/min
If 5.0 l/min is exceeded, alarm is triggered. When falling below 4.5 l/min (5 - 0.5 l/min)
the alarm is reset.
Содержание HONSBERG OMNIPLUS-F Series
Страница 1: ...Operating manual OMNIPLUS F Thermal flow sensor EN ...
Страница 21: ...OMNIPLUS F Operation 6 C E01_X__OMNIPLUS F__DB2 1 0 21 45 Overview of the parameters of the submenus ...
Страница 22: ...6 Operation OMNIPLUS F 22 45 C E01_X__OMNIPLUS F__DB2 1 0 ...
Страница 23: ...OMNIPLUS F Operation 6 C E01_X__OMNIPLUS F__DB2 1 0 23 45 ...