GHM Group
– Martens
GHM Messtechnik GmbH | Kiebitzhörn 18 | 22885 Barsbüttel | Germany
Phone +49-40-670 73-0 |
6
2.3 Brief information
Programming
The device is programmed with the buttons on the front
side in combination with the graphic display.
Operating modes
The device can be used as:
STB
→
Maximum or minimum monitoring with catch
Manual reset after fault elimination by pressing the button
on the front side or an externally connected button
ASTB
→
like before, but with exhaust temperature monitoring
STW
→
Maximum or minimum monitoring without catch
Automatic reset after return to the permissible range
Switching hysteresis
always acts towards a safe range.
Error buffer
The last error is stored as plain text and can be viewed
and deleted on the working level.
Temperature probe:
With use of the device in accordance with DIN EN 14597, temperature
sensors that are approved in accordance with DIN EN 14597 must be
used!
DANGER