background image

Pos: null /BA_Module/BA_AA  Deckblatt/BAAA000001_M003 @ 17\mod_1444211755814_28.docx @ 891110 @  @ 1 

 

 

 

 

 

Installation Instructions

 

ELEKTROMAT 
FT 60.4-45,00

 

Model: 10003292 00011

 

 

 
 
 
 
 
 
 
 
 

 

-en- 

 

Status: 24.02.2020

 

Pos: null /BA_Module/BA_Seitenumbruch @ 0\mod_1190719383361_0.docx @ 550 @  @ 1 

 

 

Содержание 10003292 00011

Страница 1: ...Deckblatt BAAA000001_M003 17 mod_1444211755814_28 docx 891110 1 Installation Instructions ELEKTROMAT FT 60 4 45 00 Model 10003292 00011 en Status 24 02 2020 Pos null BA_Module BA_Seitenumbruch 0 mod_...

Страница 2: ...BACA000001_M002 15 mod_1416821436083_28 docx 864410 1 GfA ELEKTROMATEN GmbH Co KG Wiesenstra e 81 D 40549 D sseldorf www gfa elektromaten de info gfa elektromaten de Pos null BA_Module BA_Seitenumbru...

Страница 3: ...on 12 8 Limit switch connection 13 9 Emergency manual operation lever 14 10 Completing commissioning inspection 15 11 Declaration of incorporation Declaration of conformity 16 Pos null BA_Module BA_Se...

Страница 4: ...ation shall be rendered null and void Safety information Installation and initial operation tasks are to be performed by trained skilled fitters only Only trained electrical craftsmen are permitted to...

Страница 5: ...er hour 20 h 1 Class of protection IP 65 Limit switch range maximum revolutions of output shaft hollow shaft 1 Temperature range 10 40 60 C Pos null BA_Module BA_FC Temperaturbereich BAFC000001_M002 2...

Страница 6: ...ansmission elements must not be exceeded even for maximum holding torques or locking torques refer to technical data Connection elements Self locking connection elements with a minimum strength of 800...

Страница 7: ...7 Mounting Four holes are provided for mounting...

Страница 8: ...fficient load carrying capacity Tighten all connection elements M12 to 75 Nm Install all other connection elements according to the specifications of the door manufacturer BAGAE06401_Z001 75 Nm 8 8 8...

Страница 9: ...e cables are de energised Observe the applicable regulations and standards Make a proper electrical connection Use suitable tools Performing electrical installation Remove the cover Insert the motor p...

Страница 10: ...positions for OPEN and CLOSE Prerequisite The door must open when the OPEN pushbutton is operated If the door closes L1 and L2 must exchanged with the current switched off Adjusting the OPEN limit po...

Страница 11: ...e OPEN final limit position presets the OPEN SAFETY limit switch The door must stop safely if the direction of rotation is wrong or the OPEN limit switch S3 fails If necessary carry out fine adjustmen...

Страница 12: ...x 570 1 1 6 Motor connection M1 Motor X13 Motor plug Pos null BA_Module BA_MC Alternativer Motoranschluss BAMC011001_M001 0 mod_1271681105421_28 docx 518476 1 1 7 Alternative motor connection M1 Motor...

Страница 13: ...Limit switch connection F10 Thermal contact S9 Release switch X12 Limit switch board S1 Safety open limit switch S2 Safety close limit switch S3 Open limit switch S4 Close limit switch S5 Additional l...

Страница 14: ...a means of opening or closing doors that do not have electric power supply Operation interrupts the control voltage Electrical operation is no longer possible Warning Injury through improper operatio...

Страница 15: ...mounts screws locking rings etc are secure and in proper condition Electrical wiring Check the connection cables and cabling for damage or crushing Check that the screw connections and plug connectio...

Страница 16: ...in which it has been installed complies with the provisions of the above mentioned directives Authorised representative to compile the technical documents is the undersigned D sseldorf 10 08 2018 Ste...

Отзывы: