GF Signet 2536 Скачать руководство пользователя страница 1

Iron 

strap-on

saddles

Type

Description

• 2 to 4 in., cut 1-7/16 in. hole in pipe

• Over 4 in., cut 2-1/4 in. hole in pipe

• Special order over 12 in.

• 0.5 to 4 in. versions 

• PVC or CPVC

• Mounts via glue-on fittings

Plastic tees

PVC glue-on

saddles

(O-ring not

required)

• 2 to 4 in., cut 1-7/16 in. hole in pipe

• 6 to 8 in., cut 2-1/4 in. hole in pipe

• Align wedge arrows with saddle arrows during assembly.

• Pipes over 8 in., use iron saddle

• 0.5 to 2 in. versions

• Mounts on threaded pipe ends

Carbon steel 

threaded tees

Carbon steel 

weld-on

weldolets

• 2 to 4 in., cut 1-7/16 in. hole in pipe

• Over 4 in., cut 2-1/4 in. hole in pipe

• Remove insert before welding

• Installed by certified welder only

• Special order over 12 in.  

Metric plastic saddle

• For pipes DN 65 to 200 mm

• Requires a 30 mm diam. hole in the pipe

• Wedge and saddle arrows must match

Metric wafer fitting

• For pipes DN 65 to 200 mm

• Follow the recommended installation guidelines

Metric union fitting

• For pipes from DN 15 to 50 mm

• PP or PVDF

• Follow the recommended installation guidelines

Type

Description

3-2536.090-1

1.  Location of Fitting

Recommended sensor upstream/
downstream mounting requirements.

2. Sensor Mounting Position

• Horizontal pipe runs: Mount sensor in the upright (0

°

) position for best overall performance. Mount at a

maximum of 45

°

 when air bubbles are present. Do not mount on the bottom of the pipe when sediments

are present.

• Vertical pipe runs: Sensor must be mounted in lines with UPWARD flow only.

3. Sensor Wiring

+GF+ SIGNET 2536/3-8512-XX Low Flow Sensor

4. +GF+ SIGNET Fittings

ENGLISH

SAFETY INSTRUCTIONS

1. Do not remove from pressurized lines.

2. Do not exceed maximum temperature/pressure specifications.

3. Do not install/service without following installation instructions (see sensor manual).

4. Wear safety goggles and faceshield during installation/service.

5. Do not alter product construction.

6. Failure to follow safety instructions could result in severe personal injury!

• Use 2-conductor shielded cable for cable extensions up to 

300 m (1000 ft).

• Cable shield must be maintained through cable splice.
• +GF+ SIGNET Intelek-Pro, use 2536 input card setting
• Refer to you instrument manual for specific wiring details.

black (3.3 to 24 VDC)

red (signal out)

silver (DC return)

2536/3-8512-XX 

Sensors

2536 Sensor

Input

Gnd.

10 k

 

+

3.3 to 24

VDC

-

black  

silver

red

• Pull-up resistor required (10 k

 recommended).

• Use 2-conductor shielded cable for cable extensions up to 

300 m (1000 ft).

• Cable shield must be maintained through cable splice.

Other

instrument

Blk, Sensor 

Power
Red, 

Freq. input
Shld

Gnd

+GF+ SIGNET instrument

Other Brands

10x I.D.

5x I.D.

Inlet

Outlet

Flange

15x I.D.

5x I.D.

Reducer

20x I.D.

5x I.D.

90

°

 Elbow

50x I.D.

5x I.D.

40x I.D.

5x I.D.

25x I.D.

5x I.D.

2 x 90

°

 Elbow

2 x 90

°

 Elbow

3 dimensions

Valve/Gate

B-4/98

+45

°

-45

°

0

°

Process
Pipe