15
Instruction manual
5.5
Modbus board configuration
Parameter
No.
Address(hex) Reg. Size
Read/Write
Default
Type
Description
SLAVE_ADR
0
0x2328
1
RD/WR
1
UINT8
1-247
BAUDRATE
1
0x2329
1
RD/WR
6
UINT8
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 19200 baud
7 = 38400 baud
8 = 57600 baud
9 = 115200 baud
DATABITS
2
0x232A
1
RD
8
UINT8
8 = 8 Data Bits
PARITY
3
0x232B
1
RD/WR
1
UINT8
0 = PAR_NONE
1 = PAR_EVEN
2 = PAR_ODD
STOPBIT
4
0x232C
1
RD/WR
1
UINT8
1 = STOP_1
2 = STOP_2
Remarks:
Changing of a parameter is only possible if the new value is in the allowed range (see descrip-
tion). These registers are non-volatile. For the new settings to become effective a reset
(Power-cycle the EA) is required.
Note the address gap between the board configuration registers and normal operation
registers.
Register # 49001 refers to register holding register address 9000 (2328(hex)).
The Modbus RTU board configuration can be reset to its default values (see Table above) by
triggering a factory reset on the Electric Actuator base-board (see user manual of the Electric
Actuator).