Connection possibilities for actuation elements
all known approach monitor elements can be connected, e.g.:
Radar movement detector for temperature-independent response,
even direction sensing
Infra-red movement detector
Passive infra-red movement detector
Pushbuttons of all kind, such as Code-card reader, key-operated switch, radio control
unit etc.
Door opener:
24 V DC open-circuit or closed-circuit principle *)
24 V AC open-circuit principle
Lock switch contact:
Must be installed in strikeplate if the door is locked manually
Internal programme switch
(external as an option) also available as
key-operated programme switch, with
3 positions:
- Off
- Automatic operation
- Permanently open
*) Explanation:
Open-circuit principle
Typical application: entrance door, compulsory for fire-proof doors
The locking process is made by the open-circuit principle, i.e. the door remains closed as long as the
lock is not live or actuated. The door is unlocked either by short-term actuation or permanent contact
(permanently open). In the case of power failure the door remains locked and can only be opened
mechanically via the cylinder or the door handle.
Closed-circuit principle
Typical application: RWS system
The door is locked as long as the system or the door opener is live. To open the door the circuit is
closed for a short time by willingly breaking the contact. The holding magnet of the door opener falls
off and the door is released.
Breaking of circuit means permanently open.
In the case of power failure the door is forcibly unlocked.
Available as flush or surface-mounted version