7
End connections
Function
The equipment is available with the following end
connections:
The humid and impure steam or air flows along the
fixed helix (8) in a downward spiral. Above the
sump cover plate (9), the flow of the steam or air is
reversed, giving rise to centrifugal, impact and
swirling forces. These forces separate heavy
particles such as impurities or liquids from the
steam or air. These heavy particles are then
conveyed into the collecting chamber (10).
Flanges
Screwed sockets
Name plate
The following items are indicated on the name
plate:
The change in the direction of flow prevents them
from being drawn along by the steam or air.
Manufacturer
Type designation
Min. service temperature
Max. service temperature
Max. service pressure
Direction of flow
Mark e.g. CE, UKCA (if required)
Year of construction
Serial number
Type of vessel
Weight
Body of regulations
Test pressure
Test date
Volume
Task and function
Purpose
The TD steam drier/steam purifier is installed in
steam systems.
The equipment is used to separate water,
suspended liquids and dirt from steam.
The TP air drier/air purifier is installed in
compressed air systems.
The equipment is used to separate water,
suspended liquids and dirt from compressed air.
The equipment can function as a steam or air drier
and a steam or air purifier, either at the same time
or individually.
It separates liquids, entrained water droplets or
impurities out of the flow of steam or air, with little
loss of pressure.