Troubleshooting
Fault
Cause
Remedy
The steam trap is cold or only
hand-hot.
The shut-off valves for
condensate inlet or outlet are
closed.
Open the shut-off valves.
The condensate inlet or outlet
is dirt clogged.
Clean the pipes.
Clean the equipment.
The steam trap is blowing off
live steam.
The membrane regulator
capsule and the nozzle insert
are dirty.
There are dirt deposits in the
equipment.
Clean the membrane regulator capsule
and the nozzle insert.
Clean the strainer and the equipment.
Replace the membrane regulator capsule
and the nozzle insert.
The membrane regulator
capsule and the nozzle insert
are worn down.
The seat is leaking.
Replace the membrane regulator capsule
and the nozzle insert.
The bypass is open.
Close the bypass.