OVERLOAD –
output is overloaded by over 110%, 125% or 150%.
HIGH DC –
the LED will light as long as the DC voltage is over 430VDC.
BAT LOW –
the LED will light as long as the DC voltage is lower than
320VDC.
BAT LOW STOP –
the LED will light as long as the DC voltage is lower than
295VDC, inverter cannot start.
FAULT –
the inverter is shutdown due to abnormal conditions such as overload,
short circuit, high DC, fuse over temperature, bypass breaker on or
emergency stop.
Since these LEDs are located behind the transparent window, the user can see
them clearly without opening the door.
D: Audible (buzzer) alarm:
The user should not be expected to watch the UPS all the
time. Therefore, when abnormal conditions occur, an audible sound should be
emitted to warn the user to check the status of the UPS. The alarm buzzer will beep
under any one of the following conditions:
INVERTER IS OVERLOADED-
>110%, beep once / 3 seconds
>125%, beep once / second
>150%, beep twice / second
BACK- UP
>320VDC, beep once / 3 seconds
<320VDC, beep twice / second
<295VDC, no beeping
INVERTER IS SHORT CIRCUITED -
beep continuously
FUSE BROKEN -
beep continuously
HEAT SINK OVER TEMPERATURE -
beep continuously
HIGH DC SHUTDOWN -
beep continuously
BYPASS ON STOP -
beep continuously
1-23
Содержание T3UPS-13-20K
Страница 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Страница 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Страница 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Страница 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Страница 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Страница 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Страница 24: ...INTER PCB DIAGRAM 1 19...
Страница 31: ...1...
Страница 35: ...3 3...
Страница 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Страница 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Страница 80: ...3...
Страница 81: ......