The RCCMD Message
The RCCMD message is a text message that can be defined freely. The text box automatically shifts with the entered text as
soon as you reach the right margin. This message will then appear as an alert on a computer the RCCMD client is installed to.
RCCMD also displays a warning box on the taskbar.
RCCMD Executes
An extensive feature within RCCMD is the possibility to run own executables and batch files on a target computer.
This function is useful if scripts have to be executed right before a shutdown is triggered. It is necessary to move the file to be
executed to the installation directory of the RCCMD client. Afterwards, the CS141 provides to execute this script directly.
Note:
The screenshot shows the command helloworld.bat has been entered. In this case, the RCCMD client on the PC with the IP
address 192.168.3.1 would try to start the file hallowelt.bat directly. If you want to use other directories, you need to specify
them accordingly:
C:\skript\helloworld.bat
Please note, it is tricky to run a script on a PC that shall trigger scripts on a third device.
RCCMD Traps
RCCMD traps are data packets designed to inform about the current state of the UPS:
A data package is generated, which can be received, read out and interpreted by a corresponding software or device.
The following list contains possible variables that you can use to define RCCMD traps:
#AGENTSOFTREV
CS141 firmware version
#AUTONOMTIME
autonomy time in minutes
#BATT2OLD()
Time in months until the event "Please check batteries"
#BATT2OLD_YEARS
Battery age in years
#BATTCAP
battery capacity in%
#BATTINSTDATE
Installation date of the battery
#BATTTESTDATE
Date from the last battery test
#BATTVOLT
battery voltage in V
#CHARGECURR
charging current
#CNT_BL
Counter Battery Low
#CNT_PF
Counter Power fail
#CNT_SA
Counter Active Shutdowns
#CNT_SD
Counter Shutdowns
#CNT_TF
Counter test failure
#DATE
current date
#EVENTSTATE
status (idle, error, progress, success)
#FULLTESTDATE
date of the last full test
#GETLASTRESULT()
Results from the last test performed
#HOLDTIME
UPS hold time at 100 percent load
#IDENT_NAME
name of the SNMP webmanager
#INCURR0/1/2
Input current in A
#INFREQ0/1/2
Input frequency in Hz
#INPHASES
Number of input phases
#INPUTCURRENT0/1/2
Continuously measured current in A