80
Using the integrated Webserver, the SITESWITCH 4 enables the monitoring and the remote
control of its 4 power outputs. The power sockets can be switched on and off individually. This
can be done either manually via the HTML browser interface or UPSMON or automatically
using the EVENT manager of the CS121 - or any other network CS121 or compatible device.
When executing the action using the EVENT manager of the CS121, the power switching can
be preconfigured to run with delays or to run on a schedule. Both the UPSMON time scheduler
and the HTML time scheduler can be used to configure a power switching time schedule.
This task can also be achieved using the full version of the UNMS UPS Network Management
Software.
Note:
(only SS4, not SS4AUX) If you wish to use a UPS with your SS4 then
you must install the appropriate CS121 Firmware on your SS4. The
default Firmware on SS4 (OEMID 27) is for the usage without UPS, as
standalone remote powerswitch. For UPS usage at the SS4 you must
also be sure to set the Exchange COM Ports checkbox and then use the
configuration cable (not included) to connect the SS4 with your UPS.
Figure 96:
Exchange COM Ports 1 & 2 for SS4
7.1.1
SS4 Feature overview
4 configurable powers sockets with a breaking capacity of 230V/8A
Power socket status indicator via HTML, UPSMON, UNMS or SNMP
Control via the internal CS121 or via remote CS121 or RCCMD compatible devices
Remote control of the powers sockets via HTML Browser (Password protected)
LED-Status of the power sockets
Small metal casing with 1.5RU, designed for 19"-Rack Mountings (mounting frame included)
High breaking capacity (8A), input with IEC 16A.
Programmable power switching via the HTML and UPSMON Scheduler
Delay of alarm (e.g. UPS alarms) triggered power switching on COM1 of the CS121
7.1.2
SS4 Contents
SITESWITCH 4
16A IEC 230V power cable
2 mounting irons for 19“-Rack installation
manual for SS4
The manuals are being constantly updated and therefore the reader is encouraged to check
our
website for
a newer
download
version of the adapter manual. Check
http://www.generex.de for manual updates.
7.1.3
SS4 Installation
The power consuming devices are connected to the SS4 using IEC 250 VAC/6A plug cables.
The SS4 has 4 IEC 250VAC/6A chassis sockets that can be switched on and off separately.
Содержание CS121BL
Страница 2: ......
Страница 68: ...66 Figure 72 HTTP Status Page Socomec Transfer Switch Figure 73 HTTP Status Page Eaton Transfer Switch ...
Страница 71: ...69 Figure 76 CS121 FTP Access Figure 77 CS121 FTP Context Menu Figure 78 CS121 FTP Folders ...
Страница 107: ...105 Figure 135 Internet Explorer LAN Proxy Einstellungen ...