20
Elite Steam
+03U221903
REV
2.
1
Problem
Causes
Solutions
The humidifier does not
turn on
1
No electrical power
2
. On/off switch of the humidifier in
Position 0 (off
)
3. Control connectors improperly connect
ed
4
. Bl
own fuses
5. Transformer failure
1. Che
c
k the
s
a
f
et
y
devi
c
e
s
u
ps
t
r
eam
fro
m the humidi
fi
e
r
a
n
d the
pres
e
nc
e
of po
we
r
2
. Close the switch on the panel: position I
3. Check that connectors are properly inserted in terminal block
4
. Check the condition of fuses
5. Check that the proper voltage is connected and turned on
The humidifier does not
start operation
1
. Remote
O
N/
OF
F contact open
2
. The humidistat has not been
connected correctly
3. Humidistat failure
4
. Control signal not compatible with
the type set
5. Value measured by the sensors higher
than the corresponding set point
1
. Close
O
N/
OF
F contacts
2
. Check the
ex
ternal connection
3. Replace the humidistat
The humidifier fills with
water without producing
steam
1
. High steam back pressure
2
. Fill valve strainer clogged
3. Mineral in the fill cup
4
. Drain solenoid valve leaking
1
. Check that the steam hose is not kinked or sagging,
trapping condens
ate
2
. Clean the fill valve strainer
3. Clean the fill cup
4
. Check for voltage at the drain solenoid valve and/or drain
solenoid replacement
The humidifier wets
the duct
1
. The distributor is not installed correctly
(too near the top of the duct or the
condensate return is blocked)
2
. System over-sized
3. Humidifier active when the fan in the
duct is off
1
. Check that the steam distributor is installed correctly
2. Decrease the steam production set on the control
3. Check the connection of the d
e
vice (flow switch or differential
pressure switch)
the duct.
controling
the humid
ifier to the ventilation in
The humidifier wets the
floor below
1
. The humidifier drain is blocked
2
. The supply water or overflow circuit has
leaks
3. The condensate drain pipe does not
bring the water back to the drain pan
4
. The steam hose is not properly fastened
to the cylinder
1
. Clean the drain assembly and pan
2
. Check the entire water circuit
3. Check the correct position of the condensate drain hose in the
drain pan
4
. Check the fastening of the hose clamps on the steam outlet
T
ab. 6.a
Problem
Causes
Solutions
Water in the cylinder
turns black
1
. Minerals in the cylinder have over
concentrated and are deteriorating the
electrodes
1
. Check for sags & kinks that could trap condensate in the
steam hoses that could cause a back pressure on the cylinder
2
. Check the duct static pressure
3. Check the fill valve and inlet strainer
4
. Check the drain valve operation
5. Correct installation problems and replac
e
cylinder
Heav
y arcing occurs
within hours of startup
1
. The feed water contains large amounts
of Iron, Copper or, other conductive
contaminants
1
. Contact the factory for an optional drain timer to force
additional drains to control the minerals
2
. If you are using a softener, check the salt being used. If it
contains any additives, discontinue use, flush all lines and
convert to pure salt or unsoftened water
3. Check the electrodes in th
e
cylinder to be sure th
e
y were not
damaged in shipping
Humidifier continuously
fills and drains without
production steam
1
. Minerals have bridged the electro
d
es
2
. There is back pressure from the steam
hoses or duct
3. The flow regulator in the fill valve is bro
k
en
or out of place
4
. Water conductivity is very high
5. Water is foaming
e
xcessively
1
. Clean or replace th
e
cylinder
2
. Check the steam hoses for kinks or gullies that might be
trapping condens
ate
3. Replace the fill valve
4
. Consider using a mix of demineralized water with raw water
5. Check cylinder - replace if exhausted. If feed water contains
silica or nitrates, install a 1 micron water filter
T
ab. 6.b
6. TROUBLE SHOOTING