background image

18

Elite Steam 

+03U221903

 REV 

2.

1

Fig. 5.a

5.1 Displaying Information 

By pressing the “Reset” button for 2 seconds, the display will loop from amperage to production in % 

of the maximum production to the hour counter and back to amperage:

1

.  Amperage: the value of the current that fl

ows through the water making it boil off 

      (default display)

 

2

.  Production %: the current production expressed as a percentage of the 

capacity

.

3. Hour counter, expressed in tens: for instance, when the display shows 13 the real hour 

     value will be between 130 and 139 hours.

5.1.1  Select Signal Type

The Elite Steam is preset for the included E Series humidistat (signal type 0).  If the included humidistat is used,

this section may be omitted.  If another humidistat is used, review this section to see if changes are needed.

1. Switch Elite Steam off.

 

2

.  Press and hold both buttons “reset” and “drain” and switch Elite Steam back on.

                       When the wrench blinks,

  release the 2 buttons. 

3. Press “Reset” until the display shows 02. WARNING: DO NOT

 confirm any 

            value higher than 04. In case, press “Reset” until the display goes back to the normal 

      operating mode and restart from step 1.

4.  Press “drain” (minimum

 1 second) to confirm: the display sh

ows “P1” then  the current signal

type and 

“set”.

 1. Switch Elite Steam off.

 

2.. Press both and hold both buttons “Reset” and “Drain” , and switch Elite Steam back on.   When the

                    4

. Press “drain” (minimum 1 second) the display shows “P0” then the current Maximum Production

    Percent and "set".

5. Press “reset” to change the Maximum Production in steps of 5% between 20% and 100%.

6. Press and hold “drain” (minimum 1 second) when

 done to confirm the n

ew Maximum Production

and exit to the normal operating mode.

5.3 Activating Manual Drain

Press and hold the “drain” button on the front of the unit until the cylinder is drained.  Note: Water will

continue to flow from the tempering valve after the cylinder is empty.

5.4 Resetting the hour counter

The hour counter should be reset every time the cylinder is changed in order to reset and restart the 

internal maintenance timer:

1. Switch Elite Steam off.

 

2

. Press 

and hold 

both

buttons

“Reset” and “Drain” and switch Elite Steam back on

.  When the

wrench

 blinks;  release buttons.

                                    3. 

Press and hold

 “

r

eset” until the display shows 03. WARNING: D

O

 NO

T confirm any 

          value higher than 04. In case, press “Reset” until the display goes back to the normal 

    operating mode and restart from step 1.

 

4.

  Press “Drain” (min

inimum

1 second) to confirm: the hour counter will be rese

t at once and 

     Elite Steam will go back to the normal operating mode.

5.

OPERATING ELITE STEAM

5.2 Changing The Maximum Production

wrench blinks;

  release the 2 buttons. 

 3. Press “reset” until the display shows 01.  WARNING: DO NOT confirm any value higher than 04.  In

case, press "Reset" until the display goes back to the normal operating mode and restart from step 1.

 

5

.   Press “Reset” to change signal type between 0 and 1:

          0 = On-Off humidistat such as the GeneralAire “M” or “E” series humidistat.

          1 = external 0...10 Vdc modulating signal such as the GeneralAire ADCD series humidistat.

6.   Press “drain” (mininimum 1 second) when 

done to confirm the n

ew value of P1 and exit to the 

       normal operating mode.

7.   Switch Elite Steam off: you can now proceed with connecting the control wiring.

The maximum production can be adjusted between 20% to 100% of the humidifier's

 capacity in steps of 5% in

 

order to suit the environment characteristics

.  DS35 and RS35 Maximum production is factory set at 70%. 

 

Содержание Elite Steam DS15

Страница 1: ...Residential Steam Humidi ers User manual Elite Steam...

Страница 2: ...03U221903 REV 2 1 REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING LATCH THE CYLINDER CLAMP REMOVE BEFORE INSTALLING Warning If present remove the fo...

Страница 3: ...BEFORE beginning installation Check for shipping damage to cartons Mark the shipping waybill accordingly Open cartons and check for any hidden damage Mark the shipping waybill accordingly Check packi...

Страница 4: ...4 Elite Steam 03U221903 REV 2 1...

Страница 5: ...sic Operation 11 9 14 17 17 17 17 5 OPERATING ELITE STEAM 5 1 Displaying Information 5 2 Changing The Maximum Production 18 5 3 Activating Manual Drain 18 5 4 Resetting the Hour Counter 18 5 5 Using t...

Страница 6: ...oo much as the water fills the cylinder the drain valve 13 will be activated to drain away some water and reduce the current flow to acceptable levels Note that any time the drain valve is activated t...

Страница 7: ...ife will be accompanied by the need to replace filter elements with each cylinder change Humidity load demands have an effect on cylinder life Normal installations where humidity capacity is properly...

Страница 8: ...lons per day 12 Lbs per hour 220 240v Humidifier only Kit selection required Duct steam injection 15 gallons per day 5 5 Lbs per hour 115 120v Duct steam injection 35 gallons per day 12 Lbs per hour 2...

Страница 9: ...mm 6 E 24 m m 0 0 6 F max 0 2 Degrees Tab 3 a Millimeters Inch A B C Kilograms Pounds Weight empty Weight packaged Weight installed with water Tab 3 c Duct Steam Injection Room Steam Discharge Unit D...

Страница 10: ...102 4 600 23 5 8 35 1 3 8 69 2 3 4 48 4 0 1 5 8 5 0 2 23 7 8 3 0 1 1 8 1 7 8 61 2 3 8 16 5 8 70 2 3 4 65 21 2 60 2 3 8 23 7 8 94 3 5 8 81 31 4 50 2 9 3 8 54 21 8 24 7 8 40 1 5 8 Fig 3 f 3 2 2 Fasteni...

Страница 11: ...and conductivity of water Water Conductivity must be matched by specifications of the steam cylinder Check or know the water conductivity of the proposed site before installation Replace the steam cy...

Страница 12: ...ple fact when running the steam hose steam naturally flows uphill and condensate naturally flows downhill Run the steam hose or piping to avoid any kinks sharp elbows or low spots that could collect t...

Страница 13: ...ings show the minimum recommended distances to avoid the flow of humidified air from coming into direct contact with persons lights electrical appliances and surfaces before the steam has been totally...

Страница 14: ...nection of any simple or automatic humidistat and safety devices such as high limit humidistat air flow proving switch and remote on off The humidi er is operated by the closing of a mechanical humidi...

Страница 15: ...tches are used then a jumper must be installed between AB AB DO NOT apply any voltage to AB AB 3 6 3 Connect the ADCD humidistat for Modulating Operation To select signal modulating see Fig 3 y Connec...

Страница 16: ...s L1 L 2 GROUND Power supply and Ground connections Power supply 110 VAC 1 phase 50 60Hz 1 86kW or 230VAC 1 phase 50 60Hz 4 05kW KEY Programming port Connecting to Programming port or supervisor GND N...

Страница 17: ...eter values 11 ON OFF button 12 Reset button to reset alarms and access parameters 13 Level of output 33 66 100 14 Fan relay is activated 4 3 Starting Elite Steam Insure that the external power is tur...

Страница 18: ...aximum Production and exit to the normal operating mode 5 3 Activating Manual Drain Press and hold the drain button on the front of the unit until the cylinder is drained Note Water will continue to f...

Страница 19: ...et the alarms although still active alarms will continue to display 5 Using the E2 Humidistat 5 Press toselect OFF MANUALor AUTO mode if outdoor sensor is connected OFF mode The humidifier is turned o...

Страница 20: ...r drain is blocked 2 The supply water or over ow circuit has leaks 3 The condensate drain pipe does not bring the water back to the drain pan 4 The steam hose is not properly fastened to the cylinder...

Страница 21: ...l before touching it or use protective gloves To replace the cylinder 1 Completely drain the cylinder by pressing and holding the drain button until the cylinder is empty 2 Turn the humidi er off and...

Страница 22: ...19 BLOWER FILTER KIT 6 7536 35 20 INTERNAL STEAM DISTRIBUTOR MANIFOLD FOR ROOM VERSION 7 7537 15 3 FILL TEMPERING VALVE ASSEMBLY 110 1 7 7538 35 3 FILL TEMPERING VALVE ASSEMBLY 230 1 8 7539 15 4 DRAI...

Страница 23: ...T GRILL FOR RMB 7525 DMNKIT DUCT MOUNT KIT FOR GENERALAIRE DS35 AND DS15 7545 RMB15 REMOTE MOUNT BLOWER KIT 110 1 FOR GENERAL AIRE DS15 7540 RMB35 REMOTE MOUNT BLOWER KIT 230 1 FOR GENERAL AIRE DS35 7...

Страница 24: ...ed and operated in accordance with all appropriate manuals and wiring diagrams Replacement of routinely replaceable parts such as steam cylinders and gaskets are not covered by this limited warranty o...

Страница 25: ...Elite Steam 03U221903 REV 2 1 25...

Страница 26: ...Elite Steam 03U221903 REV 2 1 NOTES 26...

Страница 27: ...Elite Steam 03U221903 REV 2 1 27...

Страница 28: ...C 43800 GRAND RIVER AVE NOVI MICHIGAN 48375 1115 WWW GENERALAIRE COM CANADIAN GENERAL FILTERS LTD 39 CROCKFORD BLVD SCARBOROUGH ONTARIO M1R3B7 WWW CGFPRODUCTS COM Agency Form 35 5 Rev 2 0 Elite Steam...

Отзывы: