Elite Steam +030222075 Rev. 3.5 – July 2012     

    

 

 

11 

3.3 

 

Plumbing 

3.3.1   Water Characteristic Requirements 

The humidifier must be supplied with water with the following characteristics: 

• pressure between 20psi and 110psi or 0.1 and 0.8 MPa (1 and 8 bar) 

• temperature between 33°F and 104°F or 1°C and 40°C 

• flow-rate minimum of 0.45 L/min or 0.21gpm 

• hardness no greater than 40°fH (equal to 400 ppm³ of CaCO), conductivity: from 125 to 1250 μS/cm 

• absence of organic compounds 

• the characteristics of the water of supply must fall within the following limits: 

 

 

LIMIT VALUES FOR LOW SALT CONTENT WATER 

 

LIMIT VALUES FOR LOW NORMAL WATER 

 

Units 

Min 

Max 

 

 

Units 

Min 

Max 

Hydrogen ions (pH) 

 

8.5 

 

Hydrogen ions (pH) 

 

8.5 

Specific conductivity (R,20°C) 

μS/cm 

300 

 

 

Specific conductivity (R,20°C) 

μS/cm 

125 

500 

Total dissolved solids (c R) 

mg/l 

(*) 

(*) 

 

Total dissolved solids (c R) 

mg/l 

(*) 

(*) 

Dry residue at 180°C 

mg/l 

(*) 

(*) 

 

Dry residue at 180°C 

mg/l 

(*) 

(*) 

Total hardness 

mg/l CaC

³

150 

400 

 

Total hardness 

mg/l CaC

³

200 

Temporary hardness 

mg/l CaC

³

200 

 

Temporary hardness 

mg/l CaC

³

150 

Iron + Manganese 

mg/l Fe + Mn 

0.2 

 

Iron + Manganese 

mg/l Fe + Mn  = 

0.2 

Chlorides 

ppm Cl 

30 

 

Chlorides 

ppm Cl 

20 

Chlorides 

mg/Si

2

20 

 

Chlorides 

mg/Si

2

20 

Chlorine residue 

mg/l Cl- 

0.2 

 

Chlorine residue 

mg/l Cl- 

0.2 

Calcium sulphate 

mg/l CaS

4

100 

 

Calcium sulphate 

mg/l CaS

4

60 

Tab.3.d  

 

 

 

 

 

 

Tab.3.e 

(*) Values dependent on the specific conductivity: in general: cR~=0.65*σR, 20°C; R180~=0.9*σR, 20°C 

Note: There is no relationship between the hardness and conductivity of water. 

 

Water Conductivity must be matched by specifications of the steam cylinder. 

Check or know the water conductivity of 

the proposed site before installation. Replace the steam cylinder before startup if not correct. See Table 3.f right. 

 

ELITE STEAM models 

Conductivity μS/cm 

Steam Cylinder 

DS25, RS25, DS25LC, RS25LC, DS35, RS35 

300-1250 

35-14 

DS25, RS25, DS25LC, RS25LC, DS35, RS35 

125-500 

35-15 

DS15P, RS15P, DS15, RS15 

125-1250 

15-14 

DS20A, RS20A 

300-1250 

20-14A 

DS20A, RS20A 

125-500 

35-14 

Tab.3.f   

 

 

The following water types are not acceptable

1. Softened water as this will lead to foam, electrode corrosion and greatly shortened 

cylinder life. 

2. Water containing disinfectants or corrosion inhibiters, as these are potential irritants. 

3. Industrial water, boiler water or water from cooling circuits. 

4. Any potentially chemically or bacteriologically contaminated water. 

5. Heated water. 

 

 

 

 

3.3.2 Water Supply Connection 

We recommend the connection between the fill valve and the water supply line by a 

soft poly hose capable of absorbing the water hammering in order to avoid damage to 

the fill valve itself. The water line may be routed through the back or through the 

bottom of the unit. With poly tubing, a tubing support must be used to prevent tubing 

collapse and leaks. The fitting then threads onto the fill valve inlet located on the 

bottom of the humidifier using a 3/4” G connection. 

Note that there is a strainer built 

into the fill valve fitting underneath the unit, which will require periodic 

cleaning, so be sure to allow clearance for access. 

 

 

 

 

 

Fill valve and filter 

Water drain 

Fig. 3.g 

Fig. 3.h 

Extension tube 

Water drain outlet 

Содержание Elite Steam DS15

Страница 1: ...Residential Steam Humidi ers User manual Elite Steam...

Страница 2: ...03U221903 REV 2 1 REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING LATCH THE CYLINDER CLAMP REMOVE BEFORE INSTALLING Warning If present remove the fo...

Страница 3: ...BEFORE beginning installation Check for shipping damage to cartons Mark the shipping waybill accordingly Open cartons and check for any hidden damage Mark the shipping waybill accordingly Check packi...

Страница 4: ...4 Elite Steam 03U221903 REV 2 1...

Страница 5: ...sic Operation 11 9 14 17 17 17 17 5 OPERATING ELITE STEAM 5 1 Displaying Information 5 2 Changing The Maximum Production 18 5 3 Activating Manual Drain 18 5 4 Resetting the Hour Counter 18 5 5 Using t...

Страница 6: ...oo much as the water fills the cylinder the drain valve 13 will be activated to drain away some water and reduce the current flow to acceptable levels Note that any time the drain valve is activated t...

Страница 7: ...ife will be accompanied by the need to replace filter elements with each cylinder change Humidity load demands have an effect on cylinder life Normal installations where humidity capacity is properly...

Страница 8: ...lons per day 12 Lbs per hour 220 240v Humidifier only Kit selection required Duct steam injection 15 gallons per day 5 5 Lbs per hour 115 120v Duct steam injection 35 gallons per day 12 Lbs per hour 2...

Страница 9: ...mm 6 E 24 m m 0 0 6 F max 0 2 Degrees Tab 3 a Millimeters Inch A B C Kilograms Pounds Weight empty Weight packaged Weight installed with water Tab 3 c Duct Steam Injection Room Steam Discharge Unit D...

Страница 10: ...102 4 600 23 5 8 35 1 3 8 69 2 3 4 48 4 0 1 5 8 5 0 2 23 7 8 3 0 1 1 8 1 7 8 61 2 3 8 16 5 8 70 2 3 4 65 21 2 60 2 3 8 23 7 8 94 3 5 8 81 31 4 50 2 9 3 8 54 21 8 24 7 8 40 1 5 8 Fig 3 f 3 2 2 Fasteni...

Страница 11: ...and conductivity of water Water Conductivity must be matched by specifications of the steam cylinder Check or know the water conductivity of the proposed site before installation Replace the steam cy...

Страница 12: ...ple fact when running the steam hose steam naturally flows uphill and condensate naturally flows downhill Run the steam hose or piping to avoid any kinks sharp elbows or low spots that could collect t...

Страница 13: ...ings show the minimum recommended distances to avoid the flow of humidified air from coming into direct contact with persons lights electrical appliances and surfaces before the steam has been totally...

Страница 14: ...nection of any simple or automatic humidistat and safety devices such as high limit humidistat air flow proving switch and remote on off The humidi er is operated by the closing of a mechanical humidi...

Страница 15: ...tches are used then a jumper must be installed between AB AB DO NOT apply any voltage to AB AB 3 6 3 Connect the ADCD humidistat for Modulating Operation To select signal modulating see Fig 3 y Connec...

Страница 16: ...s L1 L 2 GROUND Power supply and Ground connections Power supply 110 VAC 1 phase 50 60Hz 1 86kW or 230VAC 1 phase 50 60Hz 4 05kW KEY Programming port Connecting to Programming port or supervisor GND N...

Страница 17: ...eter values 11 ON OFF button 12 Reset button to reset alarms and access parameters 13 Level of output 33 66 100 14 Fan relay is activated 4 3 Starting Elite Steam Insure that the external power is tur...

Страница 18: ...aximum Production and exit to the normal operating mode 5 3 Activating Manual Drain Press and hold the drain button on the front of the unit until the cylinder is drained Note Water will continue to f...

Страница 19: ...et the alarms although still active alarms will continue to display 5 Using the E2 Humidistat 5 Press toselect OFF MANUALor AUTO mode if outdoor sensor is connected OFF mode The humidifier is turned o...

Страница 20: ...r drain is blocked 2 The supply water or over ow circuit has leaks 3 The condensate drain pipe does not bring the water back to the drain pan 4 The steam hose is not properly fastened to the cylinder...

Страница 21: ...l before touching it or use protective gloves To replace the cylinder 1 Completely drain the cylinder by pressing and holding the drain button until the cylinder is empty 2 Turn the humidi er off and...

Страница 22: ...19 BLOWER FILTER KIT 6 7536 35 20 INTERNAL STEAM DISTRIBUTOR MANIFOLD FOR ROOM VERSION 7 7537 15 3 FILL TEMPERING VALVE ASSEMBLY 110 1 7 7538 35 3 FILL TEMPERING VALVE ASSEMBLY 230 1 8 7539 15 4 DRAI...

Страница 23: ...T GRILL FOR RMB 7525 DMNKIT DUCT MOUNT KIT FOR GENERALAIRE DS35 AND DS15 7545 RMB15 REMOTE MOUNT BLOWER KIT 110 1 FOR GENERAL AIRE DS15 7540 RMB35 REMOTE MOUNT BLOWER KIT 230 1 FOR GENERAL AIRE DS35 7...

Страница 24: ...ed and operated in accordance with all appropriate manuals and wiring diagrams Replacement of routinely replaceable parts such as steam cylinders and gaskets are not covered by this limited warranty o...

Страница 25: ...Elite Steam 03U221903 REV 2 1 25...

Страница 26: ...Elite Steam 03U221903 REV 2 1 NOTES 26...

Страница 27: ...Elite Steam 03U221903 REV 2 1 27...

Страница 28: ...C 43800 GRAND RIVER AVE NOVI MICHIGAN 48375 1115 WWW GENERALAIRE COM CANADIAN GENERAL FILTERS LTD 39 CROCKFORD BLVD SCARBOROUGH ONTARIO M1R3B7 WWW CGFPRODUCTS COM Agency Form 35 5 Rev 2 0 Elite Steam...

Отзывы: