Elite Steam +030222075 Rev. 3.5 – July 2012
11
3.3
Plumbing
3.3.1 Water Characteristic Requirements
The humidifier must be supplied with water with the following characteristics:
• pressure between 20psi and 110psi or 0.1 and 0.8 MPa (1 and 8 bar)
• temperature between 33°F and 104°F or 1°C and 40°C
• flow-rate minimum of 0.45 L/min or 0.21gpm
• hardness no greater than 40°fH (equal to 400 ppm³ of CaCO), conductivity: from 125 to 1250 μS/cm
• absence of organic compounds
• the characteristics of the water of supply must fall within the following limits:
LIMIT VALUES FOR LOW SALT CONTENT WATER
LIMIT VALUES FOR LOW NORMAL WATER
Units
Min
Max
Units
Min
Max
Hydrogen ions (pH)
7
8.5
Hydrogen ions (pH)
7
8.5
Specific conductivity (R,20°C)
μS/cm
300
Specific conductivity (R,20°C)
μS/cm
125
500
Total dissolved solids (c R)
mg/l
(*)
(*)
Total dissolved solids (c R)
mg/l
(*)
(*)
Dry residue at 180°C
mg/l
(*)
(*)
Dry residue at 180°C
mg/l
(*)
(*)
Total hardness
mg/l CaC
³
O
150
400
Total hardness
mg/l CaC
³
O
0
200
Temporary hardness
mg/l CaC
³
O
=
200
Temporary hardness
mg/l CaC
³
O
=
150
Iron + Manganese
mg/l Fe + Mn
=
0.2
Iron + Manganese
mg/l Fe + Mn =
0.2
Chlorides
ppm Cl
=
30
Chlorides
ppm Cl
=
20
Chlorides
mg/Si
2
O
=
20
Chlorides
mg/Si
2
O
=
20
Chlorine residue
mg/l Cl-
=
0.2
Chlorine residue
mg/l Cl-
=
0.2
Calcium sulphate
mg/l CaS
4
O
=
100
Calcium sulphate
mg/l CaS
4
O
=
60
Tab.3.d
Tab.3.e
(*) Values dependent on the specific conductivity: in general: cR~=0.65*σR, 20°C; R180~=0.9*σR, 20°C
Note: There is no relationship between the hardness and conductivity of water.
Water Conductivity must be matched by specifications of the steam cylinder.
Check or know the water conductivity of
the proposed site before installation. Replace the steam cylinder before startup if not correct. See Table 3.f right.
ELITE STEAM models
Conductivity μS/cm
Steam Cylinder
DS25, RS25, DS25LC, RS25LC, DS35, RS35
300-1250
35-14
DS25, RS25, DS25LC, RS25LC, DS35, RS35
125-500
35-15
DS15P, RS15P, DS15, RS15
125-1250
15-14
DS20A, RS20A
300-1250
20-14A
DS20A, RS20A
125-500
35-14
Tab.3.f
The following water types are not acceptable
:
1. Softened water as this will lead to foam, electrode corrosion and greatly shortened
cylinder life.
2. Water containing disinfectants or corrosion inhibiters, as these are potential irritants.
3. Industrial water, boiler water or water from cooling circuits.
4. Any potentially chemically or bacteriologically contaminated water.
5. Heated water.
3.3.2 Water Supply Connection
We recommend the connection between the fill valve and the water supply line by a
soft poly hose capable of absorbing the water hammering in order to avoid damage to
the fill valve itself. The water line may be routed through the back or through the
bottom of the unit. With poly tubing, a tubing support must be used to prevent tubing
collapse and leaks. The fitting then threads onto the fill valve inlet located on the
bottom of the humidifier using a 3/4” G connection.
Note that there is a strainer built
into the fill valve fitting underneath the unit, which will require periodic
cleaning, so be sure to allow clearance for access.
Fill valve and filter
Water drain
Fig. 3.g
Fig. 3.h
Extension tube
Water drain outlet
Содержание Elite Steam DS15
Страница 1: ...Residential Steam Humidi ers User manual Elite Steam...
Страница 4: ...4 Elite Steam 03U221903 REV 2 1...
Страница 25: ...Elite Steam 03U221903 REV 2 1 25...
Страница 26: ...Elite Steam 03U221903 REV 2 1 NOTES 26...
Страница 27: ...Elite Steam 03U221903 REV 2 1 27...