INSTALLATION, CONTINUED
Canadian General Filters, Ltd. 400 Midwest Road Toronto, ON M1P3A9
Toll Free: (888) 216-9184
www.generalaireiaq.ca
Canadian General Filters
Limited
INSTALLING THE 120 VOLT TRANSFORMER
Note: Do not install it on a furnace supplied with a different voltage.
1. Connect the transformer primary to the relay activated when the furnace is in a heating cycle. Some furnaces have power terminals that
can be used for accessories. (Refer to the furnace installation manual.)
BASIC INSTALLATION UTILIZING THE FURNACE-SUPPLIED 24V CIRCUIT BOARD
Electronic Controller
C
G
R
W*
HSA 055
Humidistat
NO C
Dip
Switch
24V From
Furnace Circuit
Board
Valve
Valve
24 Vac
Electronic Controller
HSA 055
Humidistat
Transformer
NO C
Dip
Switch
120 Vac
Black
White
Valve
Valve
24 Vac
INSTALLING THE HUMIDISTAT
Note: Install the humidistat on the return duct. Never install below humidifier.
1. Refer to the installation manual accompanying the humidistat.
STARTING YOUR HUMIDIFIER
1. Open the water supply valve, put the furnace power back on and start the furnace in a heating cycle. Set the humidistat to the maximum setting. After
a few ON/OFF cycles of the electric valve, you should see water flowing through the drain tube. Check that the water is evenly distributed by the water
diffuser across the pad. Carefully check that both ends of the water supply tube are firmly held in place by their respective compression fitting. Set
the humidistat according to the recommended setting (40-60% RH). Check the system several times to make sure there is a free flow in the drain
tube and there is no leak before leaving the installation unattended. When everything is working fine, affix the nameplate to the humidifier cover.
MAINTENANCE
1.
Replace your
GF-
GA900
Vapor Pad
®
With Frame at the beginning of each heating season.
2.
Remove any scale buildup by soaking in vinegar and water.