INSTALLATION, CONTINUED

Canadian General Filters, Ltd.  400 Midwest Road  Toronto, ON M1P3A9

Toll Free: (888) 216-9184  

www.generalaireiaq.ca

Canadian General Filters

Limited

INSTALLING THE 120 VOLT TRANSFORMER

Note:  Do not install it on a furnace supplied with a different voltage.
1.  Connect the transformer primary to the relay activated when the furnace is in a heating cycle.  Some furnaces have power terminals that

can be used for accessories.  (Refer to the furnace installation manual.)

BASIC INSTALLATION UTILIZING THE FURNACE-SUPPLIED 24V CIRCUIT BOARD

Electronic Controller

C

G

R

W*

HSA  055

Humidistat

NO C

Dip
Switch

24V From 

Furnace Circuit 

Board

Valve

Valve

24 Vac

Electronic Controller

HSA  055

Humidistat

Transformer

NO C

Dip
Switch

120 Vac

Black

White

Valve

Valve

24 Vac

INSTALLING THE HUMIDISTAT

Note:  Install the humidistat on the return duct.  Never install below humidifier.
1.  Refer to the installation manual accompanying the humidistat.

STARTING YOUR HUMIDIFIER

1.  Open the water supply valve, put the furnace power back on and start the furnace in a heating cycle.  Set the humidistat to the maximum setting.  After

a few ON/OFF cycles of the electric valve, you should see water flowing through the drain tube.  Check that the water is evenly distributed by the water
diffuser across the pad.  Carefully check that both ends of the water supply tube are firmly held in place by their respective compression fitting.  Set
the humidistat according to the recommended setting (40-60% RH).  Check the system several times to make sure there is a free flow in the drain
tube and there is no leak before leaving the installation unattended.  When everything is working fine, affix the nameplate to the humidifier cover.

MAINTENANCE

1.

Replace your 

GF-

GA900 

Vapor Pad

®

  With Frame at the beginning of each heating season.

2.

Remove any scale buildup by soaking in vinegar and water.