MX341 AUTOMATIC VOLTAGE 

REGULATOR (AVR) 

SPECIFICATION, INSTALLATION AND ADJUSTMENTS 

General description

 

 

Technical specification

 

MX341 is a two phase sensed Automatic Voltage 
Regulator and forms part of the excitation system for a 
brush-less generator. Excitation power is derived from a 
three-phase permanent magnet generator (PMG), to 
isolate the AVR control circuits from the effects of non-
linear loads and to reduce radio frequency interference on 
the generator terminals. Sustained generator short circuit 
current is another feature of the PMG system. 
 
The AVR senses the voltage in the main generator 
winding and controls the power fed to the exciter stator 
and hence the main rotor to maintain the generator output 
voltage within the specified limits, compensating for load, 
speed, temperature and power factor of the generator. 
 
Soft start circuitry is included to provide a smooth 
controlled build up of generator output voltage. 

 

A frequency measuring circuit continually monitors the 
shaft speed of the generator and provides under-speed 
protection of the excitation system by reducing the 
generator output voltage proportionally with speed below 
a pre-settable threshold. A further enhancement of this 
feature is an adjustable volts per Hertz slope to improve 
engine recovery time on turbo charged engines. Soft start 
circuitry is included to provide a smooth controlled build 
up of generator output voltage. 
 
Uncontrolled excitation is limited to a safe period by 
internal shutdown of the AVR output device. This 
condition remains latched until the generator has 
stopped. 
 
Provision is made for the connection of a remote voltage 
trimmer, allowing the user fine control of the generator's 
output. 
 
An analogue input is provided allowing connection to a 
STAMFORD Power Factor controller or other external 
devices with compatible output. 
 
The AVR has the facility for droop CT connection, to allow 
parallel running with other similarly equipped generators. 

 

 

 

 

SENSING INPUT 

 

Voltage 

190-264V ac max, 1 phase, 2 wire 

 

Frequency 

50-60 Hz nominal 

POWER INPUT (PMG) 
 

Voltage 

140-220V ac max, 3 phase, 3 wire 

 Current  3A/phase 
 

Frequency 

100-120 Hz nominal

 

OUTPUT 

 

Voltage 

max 120V dc 

 

Current 

continuous 2.7 A 

 

 

Intermittent 6A for 10 secs. 

 

Resistance 

15 ohms minimum 

REGULATION 

 

+/- 1% 

(see note 1)

 

THERMAL DRIFT 

 0.03% 

per 

o

C  change in AVR ambient (note 2) 

SOFT START RAMP TIME 

 3 

seconds 

TYPICAL SYSTEM RESPONSE 
 

AVR Response  

10 ms 

 

Filed current to 90% 

80 ms 

 

Machine Volts to 97% 

300 ms 

EXTERNAL VOLTAGE ADJUSTMENT 
 

+/-10% with 1 k ohm 1 watt trimmer (see note 3) 

UNDER FREQUENCY PROTECTION 
 

Set point 

95% Hz (see note 4) 

 

Slope 

170% down to 30 Hz 

UNIT POWER DISSIPATION 
 

12 watts maximum 

ANALOGUE INPUT 
 

Maximum input  +/- 5V dc (see note 5) 

 

Sensitivity 

1v for 5% Generator Volts (adjustable) 

 

Input resistance  1k ohm  

QUADRATURE DROOP INPUT 

 

10 ohms burden 

 

Max. sensitivity: 0.07 A for 5% droop 0PF 

 

Max. input:  0.33 A 

OVER EXCITATION PROTECTION 
 

Set point 

75 V dc 

 

Time delay 

10 seconds (fixed) 

ENVIRONMENTAL 
 

Vibration 20-100 

Hz  50mm/sec 

 

 

100Hz – 2kHz 

3.3g 

 

Operating temperature 

-40 to +70

o

C  

 

Relative Humidity 0-70

o

C  

95% (see note 6) 

 

Storage temperature 

-55 to +80

o

C  

 

NOTES 

1. 

With 4% engine governing. 

2. 

After 10 minutes. 

3. 

Applies to Mod status D onwards. Generator de-rate may 
apply. Check with factory. 

4. 

Factory set, semi-sealed, jumper selectable. 

5. 

Any device connected to the analogue input must be fully 
floating (galvanically isolated from ground), with an 
insulation strength of 500V ac. 

6. Non 

condensing. 

 

TD_MX341.GB_

11.06_03

 

Содержание STAMFORD MX341

Страница 1: ...ltage trimmer allowing the user fine control of the generator s output An analogue input is provided allowing connection to a STAMFORD Power Factor controller or other external devices with compatible output The AVR has the facility for droop CT connection to allow parallel running with other similarly equipped generators SENSING INPUT Voltage 190 264V ac max 1 phase 2 wire Frequency 50 60 Hz nomi...

Страница 2: ...ely control the conduction period of the Power Control Devices and hence provide the excitation system with the required power to maintain the generator voltage within specified limits The Stability Circuit provides adjustable negative ac feedback to ensure good steady state and transient performance of the control system The Low Hz Detector measures the period of each electrical cycle and causes ...

Страница 3: ... case CAUTION Do not ground any of the hand trimmer terminals as these could be above earth potential Failure to observe this could cause equipment damage If a replacement AVR has been fitted or re setting of the VOLTS adjustment is required proceed as follows CAUTION 1 Before running generator turn the VOLTS control fully anti clockwise 2 Turn remote volts trimmer if fitted to midway position 3 T...

Страница 4: ...reases the amount of C T signal injected into the AVR and increases the droop with lagging power factor cos Ø With the control fully anti clockwise there is no droop TRIM ADJUSTMENT An analogue input A1 A2 is provided to connect to a STAMFORD Power Factor Controller or other devices It is designed to accept dc signals up to 5 volts CAUTION Any devices connected to this input must be fully floating...

Отзывы: