8.8.21 Starting Address Errors
The counter is incremented for each address that does not equal the device address.
A read indicates the number of Starting Address Errors that occurred in the slave
device. The maximum count is 255 and then the counter will rollover to zero and
begin counting again.
8.8.22 Number of Register Errors
A read indicates the Number of Register Errors that occurred in the slave device.
The maximum count is 255 and then the counter will rollover to zero and begin
counting again.
8.8.23 RXD CRC Hi Errors
A read indicates the number of RXD CRC Hi Byte Errors that occurred in the slave
device. The maximum count is 255 and then the counter will rollover to zero and
begin counting again.
8.8.24 RXD CRC Low Errors
A read indicates the number of RXD CRC Low Byte Errors that occurred in the slave
device. The maximum count is 255 and then the counter will rollover to zero and
begin counting again.
8.8.25 Clear Comm Errors
A Read or Write resets all the Modbus Comm Error counters to zero.