Model S4000T
36
Byte Function
Bit
Position Access
High Not
Used
15
MSB
Read
Not
Used
14
Read
Not
Used
13
Read
Not
Used
12
Read
Not
Used
11
Read
Not
Used
10
Read
Latching/Non-Latching
9 R/W
Energized/De-Energized
8 R/W
Low
Setpoint
(7-0)
R/W
8.8.8 Warn Settings
A read returns the present Warn settings of the S4000T. A write command changes
the settings to the requested values. The setpoints are programmable in 5% FS
steps. (1% FS steps for 20ppm range).
A 1 in the 9
th
bit position means the output is latching, a 0 means it is Non-Latching.
A 1 in the 8
th
bit position means the output is normally energized a 0 means it is
normally De-Energized. The Warn setpoint cannot be set above the Alarm setpoint.
Factory default is: 30% FS, non-latching, de-energized. The maximum allowable
setpoint is 50ppm.
Exception: Returns an Exception Code 01 (illegal function) if an illegal write is
requested.
Byte Function
Bit
Position Access
High Not
Used
15
MSB
Read
Not
Used
14
Read
Not
Used
13
Read
Not
Used
12
Read
Not
Used
11
Read
Not
Used
10
Read
Latching/Non-Latching
9 R/W
Energized/De-Energized
8 R/W
Low
Setpoint
(7-0)
R/W
8.8.9 Com1 Address
A read command returns the current address for Com1. A write command changes
the address to the requested value. Valid addresses are 1-247 decimal.
Factory
default is
1
.
Exception: If the address is not in range an Illegal data value (03) is returned.