Model S4000T
26
ACTION - Ensure that the supply voltage is at least +20VDC at the Model S4000T.
NOTE -
With long supply leads, a considerable voltage drop may occur, due to the
electrical resistance of the leads. The maximum cable resistance which the Model
S4000T can tolerate is dependent on the supply voltage. A maximum of 20 ohms per
conductor (40 ohms loop), at +24VDC minimum, or a maximum of 10 ohms per
conductor (20 ohms loop), at +20VDC minimum.
6.1.6 F7 - EEPROM Verification Failure
This fault occurs when an attempt to verify the setup/calibration parameters just
written to the EEPROM memory fails.
ACTION - The unit must be returned to the factory or authorized service center for
repair.
6.1.7 F8 - Failure to Complete Setup
This fault occurs if the unit is left in setup mode for more than 6 minutes.
ACTION - Exit setup mode. Enter setup mode again if it is necessary, to change any
user selectable options.
6.1.8 F9 - Gas Check Period Exceeded
If the Model S4000T is left in the gas check mode for more than twelve minutes with
Test Gas applied, this fault will occur.
ACTION - Place the magnet over the GM Logo on the cover to return the unit to
normal operation.
NOTE -
Anytime a sensor is replaced, the unit should be disconnected from all
alarms, as the unit may go upscale upon power-up.
6.1.9 F10 – Switch Error
This fault occurs if either the remote test, remote calibrate, or magnetic switch are
closed for more than two minutes.
ACTION – Check the wiring on the Remote Reset and Remote Calibrate switches.
Once the short circuit is cleared, the unit will return to normal operation. If the
magnetic switch is shorted, the unit must be returned the the factory or authorized
service center for service.