Model S4000T
5
3.3.1 Remote mounting of the Sensor from the Electronics
If it is necessary to remotely mount the sensor from the electronics and the housing,
the maximum distance can be no greater than 3700 feet (1125) meters, using 14
AWG wire. Sensors that are remotely mounted, must be placed in an explosion-proof
rated sensor housing (GM P/N 10252), and the cable run must be contained in a
conduit running from the sensor housing to the electronics. See Section 9.5, for
FMRC approval requirements.