Model S4000T
Quick Start Guide
ix
FROM
TO
Model
S4000T
Model
DT210
Model
DT230
Model
TA202A
TB2-8
“COM”
Rear
COMMON
Rear
Pin 3 or 6
“COM”
Rear
Pin 30d or
30z
Figure 5 Ground or Common Connections
FROM
TO
Model
S4000T
Model
DT210
Model
DT230
Model
TA202A
TB2-9
“+24
VDC”
Rear
CH 1 – 8
24V
Rear
Pin 4 or 7
“DC OUT”
Rear
Pin 28d or
28z
Figure 6 Power Connections
1.3.4 Analog Signal Connections
A 4 to 20mA output signal is provided by the Model S4000T Intelligent Transmitter.
This signal can be sent up to 9000 feet (2740 meters) using 14 AWG wire to:
•
A General Monitors readout/relay display module, or
•
An industrial analog to digital converter, or
•
A computer-based monitor,
•
A PLC, or
•
A DCS.
To connect the 4 to 20mA output signal with another unit, connect the wire into TB2,
position 1, labeled “4-20mA”. For making output signal connections to display
devices, refer to the specific manual for that device (Figure 7).
FROM
TO
Model
S4000T
Model
DT210
Model
DT220
Model
DT230
Model
TA202A
TB2-1
4-20mA
Output
Rear
CH 1 – 8
4-20mA
Rear
TB1
Pin 8 or 9
Rear
Pin 2 or 5
Analog In
Rear
Pin 26d
or 26z
Figure 7 Analog Signal Connections
If a device other than a General Monitors readout/relay display module is being
used, the DC ground, COM, of both systems must be connected together.