S4000C
38
Cable Requirements:
3-wire shielded cable. Max. distance between S4000C and power source @ 24VDC nominal
(20 ohm loop):
AWG
FEET
METERS
14 3430 1040
16
1900
580
18 1500
460
20
1000
300
Table 17: 24VDC Cable Lengths
Max. distance for analog output (650 ohms max):
AWG
FEET
METERS
14 9000 2740
16
5200
1585
18 3800 1160
20
2400
730
Table 18: Analog Output Cable Lengths
Max. Distance between the transmitter and sensor with one-way resistance of 20Ohms (40-
Ohm loop):
AWG
FEET
METERS
14 7600 2320
16
4800
1460
18 3000
910
20
1900
580
Table 19: Sensor Cable Lengths
European Union (EU) Approved Applications:
PSU noise and ripple voltage 1.0Vpp max. The
customer supplied PSU must comply with
IEC
61010-1, limiting current to 8A under Fault
conditions, in order to comply with CE Marking requirements.
9.3.4 Environmental
Specifications
Operating Temperature Range:
CSA/FM/ATEX
:
Electronics
-40°F to 167°F (-40°C to +75°C)
Standard Sensor
-65°F to 200°F (-55°C to +93°C)
High Temp Sensor
-65°F to 400°F (-55°C to +200°C)
ATEX:
Electronics (T5)
-40° F to 158° F (-40°C to +70°C)
Storage Temperature Range:
-58°F to 185°F (-50°C to +85°C)
Operating Humidity Range:
5% to 100% RH, non-condensing
Atmosphere:
Will not operate in <5% Oxygen
Oxygen enriched reading may be slightly higher