S4000C
16
magnet in place will cause the display to advance rapidly after a few seconds. Once the desired
value is displayed, wait 3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to
return to the next level of the Setup menu. When “
Fi
” is displayed again, apply and remove the
magnet to return to normal operation.
The default calibration level is 50% LEL
.
4.4.3 Warning Relay Settings
To adjust the Warning Relay Settings of the Model S4000C, apply the magnet to the GM Logo
on the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the unit into
Setup Mode. After a few seconds “
Lo
” will be displayed. Apply and remove the magnet to
change the Warning or “Low” alarm settings.
First, the Energized/De-Energized state of the relay is shown by either “
En
” or “
dE
” being
displayed, respectively. Apply and remove the magnet until the desired state is displayed.
After a few seconds, the Latching/Non-Latching state of the relay is shown by either “
La
” or
“
nL
”. Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the current Warning relay set point is displayed. Apply and remove the
magnet, until the desired set point is displayed. Once the desired set point value is displayed,
wait 3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to return to the next
level of the Setup menu. When “
Fi
” is displayed again, apply and remove the magnet, to return
to normal operation.
The default Warning relay settings are: non-latching, de-energized, 30% LEL set point.
NOTE:
The Warn relay set point cannot be set higher than the Alarm Relay set point, or higher
than 60% LEL.
4.4.4 Alarm Relay Settings
To adjust the Alarm Relay Settings of the Model S4000C, apply the magnet to the GM Logo on
the cover of the unit until “
SE
” is displayed, then remove the magnet. This puts the unit into
Setup Mode. After a few seconds “
Hi
” will be displayed. Apply and remove the magnet to
change the Alarm or “High” alarm settings.
First, the Energized/De-Energized state of the relay is shown by either “
En
” or “
dE
” being
displayed respectively. Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the Latching/Non-Latching state of the relay is shown by either “
La
” or
“
nL
”. Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the current Alarm relay set point is displayed. Apply and remove the
magnet until the desired set point is displayed. Once the desired set point value is shown, wait
3 seconds and “
Fi
” will be displayed. Apply and remove the magnet to return to the next level of
the Setup menu. When “
Fi
” is displayed again, apply and remove the magnet to return to
normal operation.
The default Alarm relay settings are: latching, de-energized, 60% LEL set point.