5.0 Appendix
5.1
Specifications
5.1.1 System Specifications
Sensor Type:
Diffusion, low temp. catalytic bead
Standard industrial types: Combustible
Gas; Solvent Special; Standard and High
TemperatureVersions (See section 5.4)
Typical Life: 3 years in normal service
Warranty:
Two Years
Readout/Relay Modules (See section 5.4):
DC100
Single Channel Display
DC110
Eight Channel Display
DC120
X/P Dual Channel Display
DC130
Dual Channel Display
TA102A
Single Channel, 02 Series
Fault Conditions Monitored:
Low DC Supply, Sensor Bead Open,
Calib. Out of Range, EEPROM Failure
Accuracy:
+3% LEL at ambient
Zero Drift:
Less than 5% per year
Response Time:
With 100% LEL Methane Applied,
T50 < 10 sec. & T90 < 30 sec.
Approvals:
FM approved
CSA certified to C22.2 No.152
Cenelec certified (display only with
SST flame arrestor sensors)
CE Mark approval against EMC Directive
and Product Safety
5.1.2 Electrical Specifications
Input Power:
24 VDC @ 250mA nom., 1A during SU
20 to 30 VDC range
Output Current: (
0-22mA @ 300 Ohms max. load
)
Fault:
0.0mA
Calibration:
1.5 mA
(0.0mA optional)
0-100%LEL: 4 to 20mA
Over-range: 20 to 22mA
Electrical Classification:
Class I, Division 1, Groups B, C & D
NEMA 4x rated
Recommend Three Wire Shielded Cable:
Maximum distance between the Model
S104 and the power source.
AWG
Feet
Meters
22
750
228
20
1100
335
18
1600
488
16
2250
685
14
4500
1372
For interfacing with 250 ohm input
impedance devices, the following
maximum cable lengths apply, with
respect to the Analog Signal, with the
total loop resistance less than 300 ohms.
AWG
Feet
Meters
22
1600
488
20
2400
730
18
3800
1160
16
5200
1585
14
9000
2740
NOTE: Good design practices dictate cable
lengths conservatively shorter than the maxi-
mum given values.
17
GENERAL MONITORS
Model S104