Air Flow
You must install the chassis in a location that permits good air flow through the chassis. When
facing the front of the unit, the fans cool the internal components by drawing cool air through the
left side of the chassis and expelling warm air through the right side of the chassis. With this cooling
configuration, it is important not to block the air flow through the chassis sides.
Air flow is provided by six 55 cubic feet per minute (cfm) fans. All fans must be operational to
supply adequate air flow. The maximum temperature for air entering the chassis is 122 deg. F (50
deg. C). Failure to implement these recommendations may result in overheating.
Note
IMPORTANT! Do not position a desktop chassis directly adjacent to another. This can cause warmed air to
flow from one unit into the adjacent unit.
Power Input Modules (PIMs)
The PIMs supply AC or DC input power to the unit. Inside each PIM is a fan used to cool the LIMs
and power supplies located in the back of the unit. If a fan fails, a red LED will illuminate on the
specific module with the inoperative fan. In the event of a fan failure, the PIM must be replaced.
The individual fans are not field replaceable items.
Installiation and Replacement Procedure
Spare AC or DC PIM kits are available from the manufacturer. Use the following part numbers
when ordering.
1. To install the PIMs, slide the module in on its track until it engages the connector. Use a
standard flat-blade screwdriver to tighten the retaining screw that locks the module in place.
2. To remove the PIMs, use a standard flat-blade screwdriver to loosen the retaining screw.
Pull the module out slowly.
Note
IMPORTANT! All empty slots must have blank panels installed and both Power Input Modules must be
installed at all times to maintain proper chassis cooling, EMI shielding, ESD protection, and safety
requirements.
CAUTION
Disconnect all power input connections, AC or DC, before installing or removing a PIM.
This unit has more than one power supply cord. To reduce the risk of electric shock, disconnect both
power input connections, AC or DC, before attempting any service.
Description
Part Number
AC PIM Kit
010K387-001
DC PIM Kit
010K388-001