Generac Power Systems 5464 Скачать руководство пользователя страница 1

ENVIRONMENTAL SPECIFICATIONS

Operating Temperature .......................................................................................................................................................................... -25 º C to 60 º C

Humidity ............................................................................................................................................................................... 0  to  95% Non-Condensing

Power Supply ..........................................................................................................................................................................................+12 or +24 VDC

Power Usage ............................................................................................................................................................................................ 6 Watts typical

Power Supply .......................................................................................................................................................................................Generator Battery

Communication Line .......................................................................................................................... RS485 fully isolated twisted pair cable with shield

Maximum Cable Length .................................................................................................................................................................................... 4000 feet

Relay Output .............................................................................One NO contact (Engergized when annunciator is powered and no faults are present)

Relay Contact Rating .............................................................................................................................................................................. 30 VDC,  1 amp

STANDBY GENERATOR ACCESSORIES

21 Light Remote Annunciator

Liquid-Cooled Generator Sets

Model  5465
Model  5466
Model  5464

The  Remote  Annunciator  Panel  provides  remote  monitoring  and 
annunciation of up to 18 generator parameters using LED’s  located on 
the annunciator keypad.  It also provides two system level warnings which 
are System Ready and Communications OK.
The  Relay  panel  has  up  to  8  selectable  functions  on  form  A  relays, 
and  multiple  relay  panels  can  be  connected  for  all  18  generator 
parameters. 

The specific faults can be selected using either the DIP switches located 
on the annunciator circuit board or through a computer via the RS232 
connection on the circuit board. All relays are energized on power up and 
open during a fault condition.
Communication is via a RS485 serial data link and power is supplied by 
the generator battery (+12 VDC or +24 VDC)

Note: These units are only compatible with the H-series generator 
controller (70-150 kW)

DESCRIPTION

Отзывы: