RemoDAQ-8031A/33A/34 User’s Manual
3.16 ~AAEV
Name
:
Enable/Disable Calibration
Syntax
:
~AAEV (cr)
$ delimiter character.
AA address of reading module(00~FF)
E Enable/Disable calibration command.
V 1=Enable 0=Disable
(cr) is the terminating character, carriage return (ODh)
Response
:
!AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of response module(00~FF)
Example
:
Command
:
$010 Receive
:
?01
Perform address 01 span calibration
,
return the command is
invalid before enable calibration.
Command
:
~01E1 Receive
:
!01
Set address 01 to enable calibration
,
return success.
Command
:
$010 Receive
:
!01
Perform address 01 span calibration
,
return success.
38
Содержание RemoDAQ-8031A