RemoDAQ-8031A/33A/34 User’s Manual
3.4 $AA0
Name
:
Span Calibration
Description
:
Calibrates module to correct for gain errors.
Syntax
:
$AA0 (cr)
$ delimiter character.
AA address of the module that is to be calibrated(00~FF)
0 span calibration command.
(cr) the terminating character, carriage return (0Dh).
Response
:
!AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of the module (00~FF)
In order to successfully calibrate an analog input module’s
input range, a proper calibration input signal should be
connected to the analog input module before and during the
calibration.
Example
:
Command
:
$010 Response
:
!01
Span calibration of address 01,return success
Command
:
$020 Response
:
?02
Span calibration of address 02,return the calibration is not
enable before span calibration command
Notice
:
Command only for
RemoDAQ-8031A
26