RemoDAQ-8031A/33A/34 User’s Manual
4.
Enable calibration
5.
Apply zero calibration resistance 001.00 Ohms
6.
Perform $AA40
±
VVV.VV Command,output resistor
value 001.00
7.
Perform Zero Calibration Command$AA1
8.
Apply span calibration resistance
200.00Ohm
9.
Perform $AA30V.VVVV Command
,
output resistor
value 200.00
10.
Perform span calibration command
$AA0
Calibrate Order
:
(RemoDAQ-8033A)
1.
Connect calibration resistor to module by 3-wire RTD
2.
Apply power to the module and let it warm up for about 30 minutes
3.
Setting type
4.
Enable calibration
5.
Apply zero calibration resistance 001.00 Ohms
6.
Perform $AA4N
±
VVV.VV Command,output resistor
value 001.00
7.
Perform Zero Calibration Command$AA1N
8.
Apply span calibration resistance
200.00Ohm
9.
Perform $AA3NV.VVVV Command,output resistor
value 200.00
10.
Perform span calibration command
$AA0N
11.
0~2 channel is calibrated according to 5~10 step
Calibrate Order
:
(RemoDAQ-8034)
1.
Connect calibration resistor to module by 3-wire RTD
2.
Apply power to the module and let it warm up for about 30 minutes
3.
Setting type
4.
Enable calibration
11