RemoDAQ-8054 User’s Manual
Baud rate and checksum settings have several things in common
:
¾
They should be the same for all modules and host computer.
¾
Their setting can only be changed by putting a module in the
INIT* state.
¾
Changed settings can only take effect after a module is rebooted
To alter baudrate or checksum settings you must perform the
following steps
:
¾
Power on all components except the RemoDAQ Module.
¾
Power the RemoDAQ module on while shorting the
INIT* and GND terminals
¾
Wait at least 7 seconds to let self calibration and ranging
take effect.
¾
Configure the checksum status and/or the baud rate.
¾
Switch the power to the RemoDAQ Module OFF.
¾
Remove the grounding of the INIT* terminal and power
the module on.
¾
Wait at least 7 seconds to let self calibration and ranging
take effect.
¾
Check the settings (If the baud rate has changed, the
settings on the host computer should be changed
accordingly.)