81906_MAN_GRP-H_02-2022_ENG_pag. 44
4.6.3.1. Automatic/Manual status
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
STATUS
Controls
R/W
-
(*)
Device status to set Automatic/Manual mode.
bit
Meaning
4
Automatic (0) / Manual (1)
When switched on, the following is set:
(GRP-H-x-x-D-x-x-x-x-x-x model) Automatic mode: the state of the SSR output is selected from the
state of the command input. It is possible to switch to Manual mode (together with the setting dIG.2 =
0) to deliver the power value from the Man.P parameter.
(GRP-H-x-x-AN-x-x-x-x-x-x model) Automatic mode: the power value to be supplied is selected from
the analogue input value. It is possible to switch to Manual mode to deliver the power value from the
Man.P. parameter.
(GRP-H-x-x-I-x-x-x-x-x-x model) Manual mode: the power value to be delivered is selected from the
value of the Man.P. parameter. It is possible to switch to Automatic mode to deliver a power value =
0.0%.
(*)
Model
Default
GRP-H-x-x-D-x-x-x-x-x-x e
GRP-H-x-x-AN-x-x-x-x-x-x
0
GRP-H-x-x-I-x-x-x-x-x-x
16
4.6.3.2. Manual power percentage value
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Man.P
Status
R/W
■
%
0.0
Percent power delivered by the device in Manual mode.
min...max
: 0.0% ...100.0%
4.6.3.3. Percent value of delivered power
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
Ou.P
Status
R
%
-
Percent power delivered by the device.