81906_MAN_GRP-H_02-2022_ENG_pag. 20
4.1.1.4. Analogue input correction offset
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
oFS
Inputs
Analog input
R/W
■
s.p.
0.0
The parameter sets the analogue input correction offset.
min...max: -99.9...99.9
4.1.1.5. Analog input signal digital low-pass filter
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
FLt
Inputs
Analog input
R/W
■
s
0.1
The parameter sets the time of the low pass filter on the analogue input signal.
min...max: 0.0 ...20.0 s
4.1.1.6. Fault Action Power
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
FA.P
Controls
R/W
■
%
0.0
The parameter sets the power to be supplied in the event of an analogue input fault.
When a 4 ... 20 mA input is used and the current is less than 2 mA, the Err state is generated and the
power defined in FA.P is supplied.
min...max: 0...100.0 %
Status
4.1.1.7. Analogue input value (process variable)
Acronym
App / GF_eXpress menu
Attribute Retentive U.M.
Default
Description
P.V.
Status
R
-
s.p.
-
Analogue input engineering value read (process variable).