81901 “MSW_GPC-40/600A”_03-2021_ENG_page 110
3.28.3.
Minimum non-conduction time for ramp reactivation
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1653
629
16 bit
09.01.06
PS.oF
M
MainMenu
→
M
→
Power controls
→
PS.oF_1
R/W
■
Unsigned
Short
sec.
2
2677
09.02.06
E1
MainMenu
→
E1
→
Power controls
→
PS.oF_2
4725
09.03.06
E2
MainMenu
→
E2
→
Power controls
→
PS.oF_3
The parameter sets the minimum non-conduction time to reactivate the phase softstart ramp.
min...max:
0
...
999
3.28.4.
Maximum peak current limit during ramp
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1730
706
16 bit
09.01.06
PS.tA
M
MainMenu
→
M
→
Power controls
→
PS.tA_1
R/W
■
Float
(####.#)
Apk
see
table
2754
09.02.06
E1
MainMenu
→
E1
→
Power controls
→
PS.tA_2
4802
09.03.06
E2
MainMenu
→
E2
→
Power controls
→
PS.tA_3
The parameter sets the maximum peak current limit during the phase softstart ramp.
The default value depends on the size of the controller:
Size
GPC-M, GPC-E1, GPC-E2
Default
40 A
110.0
60 A
170.0
100 A
280.0
150 A
420.0
200 A
560.0
250 A
700.0
300 A
840.0
400 A
1130.0
500 A
1410.0
600 A
1690.0
With a three-phase load, a different PS.tA parameter value can be set
for
each module.
This allows, for example, control of an
unbalanced
three-phase load
.
min...max:
0.0
...
3275.0