12
80999D_MHW_GFW 400-600A_07-2020
_ENG
CUT OFF POWER BEFORE AND DURING FUSE SUBSTITUTION PROCEDURE
-
Unscrew the screw (1) holding the cover in place
-
Remove the cover, in the direction shown by the arrow (2).
-
The fuse is revealed (3).
-
Slacken the two bolts fixing the fuse in place with a No.19 spanner (GFW 500/600A) or a No.17 spanner (GFW 400A).
-
There is no need to remove the bolts, as the fuse is pulled out of its housing as shown by the arrows (5).
-
Insert the new fuse as shown by the arrows (6).
CAUTION: the washer must be between the bolt and the copper strap (NOT under the fuse).
-
Tighten the two nuts with a No. 19 spanner (GFW 500/600A) or a No. 17 spanner (GFW 400A), to a torque of 12 Nm.
-
Put the cover back in place, pinning down the top part first (be careful to hook it on the tooth as shown in the figure).
-
Fix the cover in place, tightening the screw in its housing (1).
2.10
r
ePlacinG
the
internal
fuse
(o
Ptional
)
Figure 6
Figure 7
Figure 8
Содержание GFW 400A