AFE200 • Instruction Manual
35
5.1.6 Connection of fans power supply
Sizes
Terminals
3220 ... 61320
No connection is necessary: the AFE’s internal power supply unit powers the fan (+24Vac).
Version before 2009/125/CE (ErP regulation)
Terminals
U3
V3
PE
31
32
Sizes
71600 ... 72500
400 kW
(1)
500 kW
(1)
(1) For each
module.
1 x 230V (±10%) 50/60Hz,
2.4A (50Hz) - 3.3A (60Hz)
Ground
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan
OK
and powered;
Open: Internal fan in over temperature alarm and/or input power supply
not available.
Power the internal fan (max 600W) with a single-phase voltage on terminals U3/V3.
Type of fan compliant 2009/125/CE (ErP)
AFE200 starting from S/N 33GD018605
U3
V3
W3
PE
31
32
3 x 400V (±10%) 50/60Hz,
1.25/1.65Arms ...
3 x 460V (±10%) 60Hz,
1.55Arms
Ground
250V/2A contact
OK fan contact management terminals 31-32:
Closed: Internal fan
OK
(also with non-powered fan)
Open: Internal fan in over temperature alarm
Power the internal fan ( 570W @400V, 930W @460V ) with a three-phase voltage on terminals U3/V3/W3.
Version before 2009/125/CE (ErP regulation)
Terminals
U3
V3
W3
PE
31
32
Sizes
73150 ... 73550
630 kW
(1)
710 kW
(1)
900 kW
(1)
1 MW
(1)
(1) For each
module.
3 x 400V (±10%) 50Hz,
1,55Arms
or
3 x 460V (±10%) 60Hz,
1,7Arms
Ground
250V/10A contact
OK fan contact management terminals 31-32:
Closed: Internal fan
OK
(also with non-powered fan)
Open: Internal fan in over temperature alarm
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
Type of fan compliant 2009/125/CE (ErP)
AFE200 starting from S/N 33GD018605
3 x 380...480V (±10%)
50/60Hz,
1.9 ... 1.7 Arms
Ground
250V/10A contact
OK inverter fan contact management terminals 31-32:
Closed: Inverter fan OK and powered;
Open: Inverter fan in alarm or not supplied.
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
Make sure the sequence of the three-phase fan power supply phases is the same as that shown on
the relative AFE terminals. If not, the air flow will be inadequate to ensure correct cooling..
Caution
Содержание AFE200 4 Series
Страница 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Страница 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Страница 202: ...202 AFE200 Instruction Manual Appendix 3 Block Diagrams System Diagrams Index Drive overview Reference ...
Страница 203: ... AFE200 Instruction Manual 203 Commands ...
Страница 204: ...204 AFE200 Instruction Manual Digital inputs ...
Страница 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Страница 206: ...206 AFE200 Instruction Manual Analog inputs ...
Страница 207: ... AFE200 Instruction Manual 207 ...
Страница 208: ...208 AFE200 Instruction Manual Analog outputs ...
Страница 209: ... AFE200 Instruction Manual 209 Current Control ...
Страница 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Страница 211: ... AFE200 Instruction Manual 211 Functions ...
Страница 212: ......
Страница 213: ......