32
ADV200
WA • Functions description and parameters list
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.2
872 Mpot acceleration
s
FLOAT
5.0
0.01
1000.00
RW VS
8.3
874 Mpot deceleration
s
FLOAT
5.0
0.01
1000.00
RW VS
Setting of the acceleration/deceleration ramp times (in seconds) used with the Motor potentiometer function.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.4
876 Mpot top lim
rpm INT16
PAR 680
CALCI
CALCI
ERW VS
Setting of the top limit for the speed reference output from the motor potentiometer.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.5
878 Mpot bottom limit
rpm INT16
0
CALCI
CALCI
ERW VS
Setting of the bottom limit for the speed reference output from the motor potentiometer.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.6
880 Mpot init cfg
ENUM
Zero
0
3
ERW VS
Use this parameter to configure the output value of the Motor potentiometer at drive start-up.
0
Last power off
1
Zero
2
Lower Limit
3
Upper Limit
When set to
Last power off
, the motor potentiometer output starts from the last frequency that was set before
the drive was switched off.
When set to
Zero
the motor potentiometer output starts from a value of 0.
When set to
Lower limit
the output of the motor potentiometer starts from the value of the lower limit set in
the
Mpot bottom limit
parameter.
When set to
Upper limit
the output of the motor potentiometer starts from the value of the upper limit set in
the
Mpot top limit
parameter.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
8.7
882 Mpot preset cfg
ENUM
None
0
11
ERW VS
This parameter can be used to configure the preset of the Motor potentiometer function, i.e. to configure the
value at which the Motor potentiometer input and output are set when the Preset command is enabled.
The Preset command has priority over the Up command and the Down command.
Mpot mode
(PAR 892) = [1]
Ramp&Follow
has priority over the Preset command, i.e. actions programmed
with
Mpot preset cfg
(PAR 882) are not executed.
The Up and Down commands are enabled again when the Preset command is disabled.
0
None
1
Input = 0
2
Input = low lim
3
Input & ref = 0
4
Input & ref = low lim
5
Output = 0
6
Output = low lim
7
Output & ref = 0
8
Output & ref = low lim
9
Input = upp lim
10
Input & ref = upp lim
11
Freeze input
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......