272
ADV200
WA • Troubleshooting
Index Error message shown
on the display
Sub-code
Description
Solution:
Remove the optional cards from the incorrect slots and insert them in the correct slots
11
Load def plc
Condition:
may occur during loading of the parameter database saved in the Flash of the Mdplc application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the param-
eter database saved in Flash.
If this message appears the drive restores the default database, i.e. the one that was downloaded.
0001H-1
The database saved is not valid
Solution:
Set the parameters to the value required and perform
Save parameter
12
Plc cfg error
Condition:
may occur during loading of the Mdplc application
The Mdplc application present on the drive is not run.
0004H-4
The application downloaded has a different Crc on DataBlock and Function table
0065H-101
The application downloaded has an invalid identifier (Info)
0066H-102
The application downloaded has an incorrect task number (Info)
0067H-103
The application downloaded has an incorrect software configuration
0068H-104
The application downloaded has a different Crc on DataBlock and Function table
0069H-105
A Trap error or System error has occurred.
The drive automatically performs a Power-up operation.
The application is not run.
See in Alarm List for further information regarding the error occurred
006AH-106
The application downloaded has an incorrect identifier (Task)
006BH-107
The application downloaded has an incorrect task number (Task)
006CH-108
The application downloaded has an incorrect Crc ( Code)
Solution:
Remove the Mdplc application or download a correct Mdplc application
13
Plc 1
Reserved messages and dedicated to the PLC application. See the application manual.
14
Plc 2
15
Plc 3
16
Plc 4
17
Option bus fault
Condition:
this may occur when the drive is turned on, during fieldbus card setup. Error during configuration or com-
munication error.
XXX0H-X
If the first digit to the left of “H” in the alarm sub-code is 0, the error regards a communication
problem.
XXX0H-X
If the first digit to the left of “H” in the alarm sub-code is other than 0, the error regards a configu-
ration problem.
Solution:
For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address,
parameter setting.
For communication errors, check wiring, termination resistors, disturbance immunity, timeout settings.
For further details, please refer to the user guide for the specific bus.
18
Key failed
Condition
: this may occur when powering the drive, if the incorrect enable key is inserted for a given firmware func-
tion.
0001H-1
Incorrect PLC key. PLC application not available.
Solution
: Ask Gefran to supply the correct key to enable the desired firmware function.
19
Key expiring
Condition:
this may occur at drive power-on if the incorrect enabling key was inserted for a given firmware function.
At this stage the firmware function can still be used freely, but this time limit is about to expire.
xxxxH-x
Number of hours for which the function can still be used freely.
Solution:
Ask Gefran for the correct key to enable the desired firmware function.
20
Param error
Condition
: if an error occurs during activation of the parameter database saved in flash; the alarm is inserted in the
alarm list and alarm log.
XXX0H-X
The code XXXXH-X indicates the IPA of the parameter that has been set outside the range allowed
when the database is enabled.
Solution
: Set the parameter causing the error to a value within the range and run
Save parameters
. Switch the drive
off and then switch it back on again.
If the IPA of the parameter is not shown in the manual, contact the service centre.
21
22
Options cfg changed
Condition
: this may occur when powering the drive if an expansion card has been removed or replaced or the incor-
rect enable key is inserted for a given firmware function.
0064H-100
Card removed from slot 1
0014H-20
Card removed from slot 2
0003H-3
Card removed from slot 3
0078H-120
Card removed from slot 1 and from slot 2
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......