ADV200 WA • Functions description and parameters list
189
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
27.2.3 11008 PID 1 ref function
ENUM
Ref1
0
5
RW VS
This parameter is used to adjust reference 1 and 2 analog input signals for the PID1 controller:
0
Ref1
1
Ref2
2
Src selection
3
Ref1+Ref2
4
Ref1-Ref2
5
Aver ref1 ref2
Set to
0
to select the value of reference signal 1 as the setpoint for the PID 1 function.
Set to
1
to select the value of reference signal 1 as the setpoint for the PID 2 function.
Set to
2
to select the value of the reference signal 1 or reference signal 2 for the PID 1 function, depending on
that selected in parameter
11010 PID 1 ref sel src
.
Set to
3
to select the result of the following formula as the setpoint for the PID 1 function:
rif1 value+(rif2 value-50% Full scale)
Set to
4
to select the result of the following formula as the setpoint for the PID 1 function:
(rif1 value+50% of Full scale)-rif2 value)
Set to
5
to select the arithmetic mean of reference 1 and reference 2 as the setpoint for the PID 1 function.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
27.2.4 11010 PID 1 ref sel src
LINK 16BIT
0 0 16384
RW
VS
Selection of the origin (source) of the PID 1 function reference signal between reference 1 and reference 2.
This setting only applies if parameter 7308
PID 1 ref function
is set to 3 (Src selection). PID controller refer-
ence signals can be selected from those listed in the “
L_PIDREF
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
27.2.5 11012 PID 1 fbk 1 src
LINK 16/32BIT
1500
0
16384
RW VS
Selection of the origin (source) of feedback signal 1 for the PID 1 function. The PID controller feedback sig-
nals can be selected from those listed in the “
L_PIDFBK
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
27.2.6 11014 PID 1 fbk 2 src
LINK 16/32BIT
0 0 16384
RW
VS
Selection of the origin (source) of feedback signal 2 for the PID 1 function. The PID controller feedback sig-
nals can be selected from those listed in the “
L_PIDFBK
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
27.2.7 11016 PID 1 fbk function
ENUM
Fbk1
0
10
RW VS
Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller:
0
Fbk1
1
Fbk2
2
Fbk1+Fbk2
3
Fbk1-Fbk2
4
Fbk1*Fbk2
5
Fbk1/Fbk2
6
Min fbk1fbk2
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......